 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING
 ARE SIX OR LESS AND GROUPED IN ONE LOCATION. CLARIFY
 THE ELECTRICAL RISER PLAN TO SHOW ALL METERS,
 GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS FOR THE
 WHOLE BUILDING LOCATED IN ONE LOCATION.
 NEC 230.2, 230.71, 230.72
  
 SHEET E002 NOTE 17 REFERS TO A 1000 AMPERE MAIN
 DISCONNECT WHICH WOULD REQUIRE GFP PROTECTION. NEC
 230.95
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE
 ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC
 215.5, 110.26
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, SITE LIGHTING, INTERIOR BUILD OUT AND
 SECURITY.
  
  