| Plan Review Notes For Permit 13071098 |
| Permit Number |
13071098 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-17 10:19:49 | 13071098 | | | 1855 PALM BEACH LAKES BLVD. #B01 | | | OUT PARCELS B12, B13,B14,B15,B16. | | | | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS BUILDING | | | ARE SIX OR LESS AND GROUPED IN ONE LOCATION. CLARIFY | | | THE ELECTRICAL RISER PLAN TO SHOW ALL METERS, | | | GROUNDING, MAIN DISCONNECTS AND PANEL BOARDS FOR THE | | | WHOLE BUILDING LOCATED IN ONE LOCATION. | | | NEC 230.2, 230.71, 230.72 | | | | | | SHEET E002 NOTE 17 REFERS TO A 1000 AMPERE MAIN | | | DISCONNECT WHICH WOULD REQUIRE GFP PROTECTION. NEC | | | 230.95 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. | | | NEC 110.22, 110.16, 110.22 | | | | | | PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE | | | ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC | | | 215.5, 110.26 | | | | | | NOTE: | | | SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE, | | | DATA, FIRE ALARM, SITE LIGHTING, INTERIOR BUILD OUT AND | | | SECURITY. | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | |
|