2013-08-25 12:40:11BUILDING PLAN REVIEW
 PERMIT: 13071098
 ADD: 1855 PALM BEACH LAKES BLDG' "B1"SHELL
 CONT: EMJ KERI NEVEL
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY AUGUST 25/ 2013
 ACTION: DENIED
  
  
 1A) PLEASE UPDATE THE PLANS TO REFLECT THE BUILDING
 ADDRESS FOR SHELL BUILDING B1 TO 1855 PALM BEACH LAKES,
 THE SITE ADDRESS IS THE 1801 PALM BEACH LAKES ADDRESS.
  
 1B) PLEASE PROVIDE A OVER ALL SITE PLAN OF THE PB
 OUTLET MALL PROPERTY AND THE LOCATION OF THIS BUILDING
 COMPLIANCE WITH THE THE 2010 FBC-B TABLE 602 & TABLE
 705.8 CAN NOT BE DETERMINED.
  
 2) APPROVAL STAMPS FROM THE PALM BEACH OUTLET MALLS IS
 REQUIRED BEFORE PERMIT SUBMITTAL, PLEASE OBTAIN THE
 APPROVAL STAMP BEFORE THE NEXT SUBMITTAL PROCESS
 BEGINS.
  
 3) PB OUTLET MALLS: BE AWARE FOR TENANT BUILD OUTS.
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 4) SHEET S.001:
 4A) UNDER THE HEADING OF COMPONENTS AND CLADDING THE
 ROOFING PRESSURE CATEGORIES ARE MISSING THE 10 SQ FT
 COLUMN. THIS IS THE HIGHEST PRESSURES TO BE TAKEN UNDER
 THE COMPONENTS AND CLADDING CHARTS. THE FASTENERS FOR
 ROOFING WE USE THE 10 SQ FT COLUMN SINCE THE FASTENERS
 ARE HOLDING THE WORST CASE SCENERIO.
  
 4B) FOUNDATIONS INDICATES THERE IS A SOILS REPORT THAT
 HAS BEEN COMPLETED, PLEASE SUPPLY REPORT BY ECS DATED
 JUNE 16/ 2012. 2010 FBC-B 1803.2 INVESTIGATION REQUIED.
  
 4C) UNDER THE HEADING TILT-UP CONCRETE WALL PANELS,
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
 110.3.9 OTHER INSPECTION SEERVICES, THIS PROJECT BEING
 TILT WALL WILL QUALIFY FOR A RESIDENT INSPECTOR. SUCH
 INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES WORK IS
 UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE BUILDING.
 SUCH INSPECTORS SHALL BE A REGISTERED ARCHITECT, OR
 ENGINEER, OR A PERSON LICENSED UNDER CHAPTER 468, PART
 XII, FLORIDA STATUTES. SUCH INSPECTORS SHALL SUBMIT
 WEEKLY PROGRESS REPORTS INCLUDING THE DAILY INSPECTIONS
 TO THE BUILDING OFFICIAL, AND INCLUDING A CODE
 COMPLIANCE OPINION OF THE RESIDENT INSPECTOR.
 PLEASE CONTACT KEN CONRAD THE DIRECTOR OF THE RESIDENT
 INSPECTOR PROGRAM FOR REQUIREMENTS FORMS AND ADDITIONAL
 INFORMATION ON THIS PROGRAM AND REQUIREMENTS :
 KEN CONRAD
 TEL: 561-805-6666
 FAX: 561-805-6676
 E-MAIL: KCONRAD @WPB.ORG
  
 5) SHEET S002 RTU HEADING THE NOTE AS FOLLOWS: GC TO
 PROVIDE PRE-ENGINEERED RTU TIE DOWNS OR EQUIVALENT
 ENGINEERED TIE-DOWN SOLUTIONS THAT MEET OR EXCEEDS TTHE
 REQUIRED WIND DESIGN CRITERIA. PLEASE PROVIDE
 ENGINEERING FOR ROOF TOP UNITS PER 2010 FBC-B 1609.8
 ROOF TOP STRUCTURES & EQUIPMENT.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) PLEASE SUBMIT THE FOLLOWING PRODUCT APPROVALS: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING DOORS, ROLL UP DOORS &
 ROOF HATCH .
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES NOTE BOTH FOR FULLY
 ADHERRED SYSTEMS AND MECHANICALLY FASTENED SYSTEMS,
 ALSO INCLUDE ROOF TOP INSULATION, & A/C CURBING.
 (G) PRE-ENGINEERED A/C STANDS IF THEY ARE GOING TO BE
 INSTALLED
  
 8) SHEET A401 WALL DETAIL A1 PROVIDES A ONE HOUR FIRE
 RATED WALL DETAIL BUT THE PLANS DOES NOT PROVIDE A FIRE
 1 HOUR FIRE RATED ASSEMLBY AT THE WALL TO ROOF
 CONNECTION.2010 FBC-B 714.1 FIRE-RESISTANT JOINT
 SYSTEM. 714.2 INSTALATION, & 714.3 FIRE TEST CRITERIA.
  
 9) PLEASE PROVIDE HOW THIS BUILDING IS GOING TO MEET
 THE 2010 FL ENERGY CODE CODE REQUIREMENTS FOR SHELL
 BUILDINGS UNDER 502.1.1.1.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved