| Notes |
| Date |
Text |
| 2013-12-14 12:06:56 | 400 CLEMATIS STREET - SUITE #103 | | | TRACKING #13071054 | | | PERMIT # 13020651 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | VENTLESS HOOD FILTERS: | | | BAFFLE FILTER CLEAN DAILY | | | PRE-FILTER REPLACE WEEKLY | | | EAC FILTER CLEAN DAILY | | | CHARCOAL FILTER REPLACE EVERY 30 DAYS | | | UV LAMP CLEAN EVERY 30 DAYS/REPLACE ANNUALLY | | | | | | HOOD: | | | PERFORM MONTHLY INTERLOCK CHECK | | | CLEAN EVERY 3 MONTHS | | | | | | SUPPRESSION SYSTEM: | | | SERVICE SYSTEM EVERY 6-MONTHS | | | REPLACE FUSIBLE LINKS ANNUALLY | | | | | | **FAILURE TO STRICTLY ADHERE TO THIS CLEANING, | | | MAINTENANCE, AND SERVICE SCHEDULE WILL RESULT IN A | | | CEASE & DESIST FOR ALL COOKING OPERATIONS.** | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|