| Plan Review Notes For Permit 13071054 |
| Permit Number |
13071054 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-09 11:25:41 | 400 CLEMATIS STREET - SUITE #103 | | | TRACKING #13071054 | | | PERMIT # 13020651 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET A1.O: THE REAR SERVICE CORRIDOR INDICATED AS | | | "PRIVATE USE ONLY" SHALL ONLY FUNCTION AS A DELIVERY | | | CORRIDOR. WALLS AND PENETRATIONS SHALL BE REPAIRED. | | | PERMANENT SIGNAGE SHALL BE POSTED INDICATING "NO | | | STORAGE PERMITTED." ADDITIONALLY, THE ILLUMINATED EXIT | | | SIGNS, DAYTIME LIGHTING AND EMERGENCY IN THIS CORRIDOR | | | NEEDS TO BE FIXED AS IT WAS VERY DARK DURING | | | INSPECTION. | | | | | | SHEET M1.01: PLANS INDICATE A NEW VENTLESS KITCHEN | | | HOOD. SUBMIT CUT SHEET INFORMATION FOR NEW HOOD. PLANS | | | SHALL INDICATE THE CLEANING AND MAINTENACE SCHEDULE | | | ASSOCIATED WITH THE VENTLESS HOOD SO THE TENANT IS | | | AWARE THIS SCHEDULE NEEDS TO BE FOLLOWED STRICLTY | | | OTHERWISE THE TENANT WILL NOT BE PERMITTED TO RESUME | | | COOKING OPERATIONS. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|