| Notes |
| Date |
Text |
| 2013-09-10 14:58:24 | 13071028 | | | 477 S ROSEMARY | | | HOTEL ROOM MOCK UP | | | | | | PERMIT MAY BE ISSUED WITH THE FOLLOWING PROVISO: | | | | | | GUEST SUITES REQUIRE A WALL SWITCH-CONTROLLED LIGHTING | | | OUTLET OR RECEPTACLE FOR THE SLEEPING AREA. NEC 210.70 | | | (B) | | | AN ADDITIONAL RECEPTACLE THAT IS READILY ACCESSIBLE IS | | | REQUIRED IN EACH BEDROOM. NEC 210.60 | | | GUEST ROOM RECEPTACLES SHALL BE TAMPER RESISTANT NEC | | | 406.13 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | |
|