Plan Review Notes
Plan Review Notes For Permit 13071028
Permit Number 13071028
Review Stop P
Sequence Number 1
Notes
Date Text
2013-08-09 08:37:49FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A1.01 SHOWS WHAT APPEARS TO BE AN OFFICE AREA
 WITH 2 ACCESSABLE RESTROOMS. THE RESTROOMS WOULD NOT
 MEET THE REQUIREMENTS OF THE FBC ACCESSIBILITY CODE
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.8.1.6 LAVATORY.
 IN NEW CONSTRUCTION, THE WHEELCHAIR ACCESSIBLE TOILET
 COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN
 IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17 INCHES
 DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 604 FOR THE WHEELCHAIR
 ACCESSIBLE TOILET COMPARTMENT AND SHALL COMPLY WITH
 SECTION 606. SUCH LAVATORIES SHALL BE COUNTED AS PART
 OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE
 ALSO SECTION 213.3.4.
  
  