| Plan Review Notes For Permit 13071028 |
| Permit Number |
13071028 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-09 07:03:38 | ALL OF THE BELOW LISTED ITEMS MAY BE ADDRESSED BY A | | | COVER LETTER, NOTE ON THE PLAN OR CONVERSATION WITH THE | | | REVIEWER AND PROVISOS BEING ADDED. | | | DOUG HARVEY | | | [email protected] | | | 561-805-6740 | | | | | | THANK YOU | | | | | | PLEASE PROVIDE ASSA ABLOY LISTING DATA FOR LOCKSETS IF | | | ELECTRICAL LOCKS WILL BE PUT IN MODEL | | | PROVIDE GFCI FOR DEMOLITION (MAY BE DONE WITH A NOTE) | | | 590.4 | | | PROVIDE LIGHTING FOR DEMOLITION (MAY BE DONE WITH A | | | NOTE) 590.4 | | | LIGHTING AND POWER TO BE ON SEPARATE CIRCUITS 590.4 D | | | TEMPORARY POWER TO COMPLY WITH NEC ARTICLE 590 | | | PLAN E4.0 CALLS FOR CAPPING ELECTRICAL OUTLETS ABOVE | | | CEILING. IF OUTLETS ARE NOT CONNECTED, WHY ARE THEY RUN | | | TO ABOVE THE CEILING? ARE OUTLETS BEING INSTALLED OR | | | REMOVED, OR ARE EXIATING OUTLETS REMAINING FOR FUTURE | | | RECONNECTION? | | | OUTLET HEIGHT IS NOT IN CONFORMANCE WITH FAIR HOUSING | | | GUIDELINES AS GENERALLY USED FOR ACCESSIBLE ROOMS. WILL | | | ADDITIONAL ROOMS IN COMFORMITY BE SPELLED OUT LATER OR | | | WILL THESE GUIDELINES BE CONSIDERED AS NON-APPLICABLE? | | | |
|