2013-08-09 07:03:38ALL OF THE BELOW LISTED ITEMS MAY BE ADDRESSED BY A
 COVER LETTER, NOTE ON THE PLAN OR CONVERSATION WITH THE
 REVIEWER AND PROVISOS BEING ADDED.
 DOUG HARVEY
 [email protected]
 561-805-6740
  
 THANK YOU
  
 PLEASE PROVIDE ASSA ABLOY LISTING DATA FOR LOCKSETS IF
 ELECTRICAL LOCKS WILL BE PUT IN MODEL
 PROVIDE GFCI FOR DEMOLITION (MAY BE DONE WITH A NOTE)
 590.4
 PROVIDE LIGHTING FOR DEMOLITION (MAY BE DONE WITH A
 NOTE) 590.4
 LIGHTING AND POWER TO BE ON SEPARATE CIRCUITS 590.4 D
 TEMPORARY POWER TO COMPLY WITH NEC ARTICLE 590
 PLAN E4.0 CALLS FOR CAPPING ELECTRICAL OUTLETS ABOVE
 CEILING. IF OUTLETS ARE NOT CONNECTED, WHY ARE THEY RUN
 TO ABOVE THE CEILING? ARE OUTLETS BEING INSTALLED OR
 REMOVED, OR ARE EXIATING OUTLETS REMAINING FOR FUTURE
 RECONNECTION?
 OUTLET HEIGHT IS NOT IN CONFORMANCE WITH FAIR HOUSING
 GUIDELINES AS GENERALLY USED FOR ACCESSIBLE ROOMS. WILL
 ADDITIONAL ROOMS IN COMFORMITY BE SPELLED OUT LATER OR
 WILL THESE GUIDELINES BE CONSIDERED AS NON-APPLICABLE?
  