2013-08-09 17:49:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE ROOM/USE DESIGNATIONS FOR THE AREAS EAST OF
 THE GUESTROOM CORRIDOR FBC 107.
  
 2. THE FOLLOWING DOORS LACK MANEUVERING CLEARANCE FBC
 2010 ACCESSIBILITY FIGURE 404.2.4.1:
  
 NORTH BATHROOM VESTIBULE
 NORTH ENTRY DOOR (PLAN STATES THAT THE EXISTING FRAMED
 PARTITION IS TO REMAIN, BUT NOT CLEAR WHY THIS DOOR
 DOES NOT APPEAR TO COMPLY; IS THERE AN AUTOMATIC DOOR
 OPENER AT THIS LOCATION?)
 SOUTH ENTRY DOOR
  
 3. FBC 2010 ACCESSIBILITY FIGURE 404.2.6, SHOW DISTANCE
 BETWEEN EDGE OF FIRST DOOR AND SECOND DOOR FROM ENTRY
 TO STORAGE DOOR MARKED D1 (DOORS IN SERIES).
  
 4. SHEET A1.00 SHOWS A MAX TRAVEL DISTANCE OF 86'.
 PLEASE SHOW DEAD END TRAVEL DISTANCE. IT IS NOTED AS
 MAX 50', BUT NO DIMENSION SHOWN FOR THE DEAD END,
 1018.4 (DOOR D1 TO SW CORNER).
  
 5. PLAN STATES THAT EXISTING USE IS BUSINESS. THE
 ORIGINAL BUILDING PERMIT WAS FOR RESIDENTIAL ON THE 2ND
 AND 3RD FLOORS. I WAS UNABLE TO LOCATE A CHANGE OF
 OCCUPANCY FOR THIS SPACE. I WAS ALSO UNABLE TO LOCATE A
 BUSINESS TAX RECEIPT FOR A BUSINESS FOR THIS UNIT.
  
 6. PLEASE SEE PLUMBING NOTES REGARDING BATHROOM
 ACCESSIBILITY.
  
 7. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY MAY BE
 REQUIRED. 233-5025 FOR MORE INFORMATION.
  
  
  