| 2013-08-09 17:49:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE ROOM/USE DESIGNATIONS FOR THE AREAS EAST OF | | | THE GUESTROOM CORRIDOR FBC 107. | | | | | | 2. THE FOLLOWING DOORS LACK MANEUVERING CLEARANCE FBC | | | 2010 ACCESSIBILITY FIGURE 404.2.4.1: | | | | | | NORTH BATHROOM VESTIBULE | | | NORTH ENTRY DOOR (PLAN STATES THAT THE EXISTING FRAMED | | | PARTITION IS TO REMAIN, BUT NOT CLEAR WHY THIS DOOR | | | DOES NOT APPEAR TO COMPLY; IS THERE AN AUTOMATIC DOOR | | | OPENER AT THIS LOCATION?) | | | SOUTH ENTRY DOOR | | | | | | 3. FBC 2010 ACCESSIBILITY FIGURE 404.2.6, SHOW DISTANCE | | | BETWEEN EDGE OF FIRST DOOR AND SECOND DOOR FROM ENTRY | | | TO STORAGE DOOR MARKED D1 (DOORS IN SERIES). | | | | | | 4. SHEET A1.00 SHOWS A MAX TRAVEL DISTANCE OF 86'. | | | PLEASE SHOW DEAD END TRAVEL DISTANCE. IT IS NOTED AS | | | MAX 50', BUT NO DIMENSION SHOWN FOR THE DEAD END, | | | 1018.4 (DOOR D1 TO SW CORNER). | | | | | | 5. PLAN STATES THAT EXISTING USE IS BUSINESS. THE | | | ORIGINAL BUILDING PERMIT WAS FOR RESIDENTIAL ON THE 2ND | | | AND 3RD FLOORS. I WAS UNABLE TO LOCATE A CHANGE OF | | | OCCUPANCY FOR THIS SPACE. I WAS ALSO UNABLE TO LOCATE A | | | BUSINESS TAX RECEIPT FOR A BUSINESS FOR THIS UNIT. | | | | | | 6. PLEASE SEE PLUMBING NOTES REGARDING BATHROOM | | | ACCESSIBILITY. | | | | | | 7. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY MAY BE | | | REQUIRED. 233-5025 FOR MORE INFORMATION. | | | | | | | | | |
|