| Plan Review Notes For Permit 13071001 |
| Permit Number |
13071001 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-08 16:17:13 | PERMIT # 13071001 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | ***PROVISO*** | | | | | | | | | 1. PLEASE CLARIFY IF STRUCTURE WILL BE CONSIDERED A | | | SEPARATE BUILDING OR INCORPORATED INTO MAIN STRUTURE. | | | IF IT IS TO BE CONSIDERED AS PART OF THE MAIN | | | STRUCTURE, SEPARATE PLANS WILL NEED TO BE SUBMITTED FOR | | | SPRINKLER SYSTEM AND FIRE ALARM. | | | 2. STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS | | | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO | | | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS | | | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED | | | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF | | | DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA | | | ADMINISTRATIVE CODE 69A-60.0081. | | | 3. HOOD EXHAUST MUST BE 10 FEET FROM THE PROPERTY LINE. | | | | | | | | | | | | LAUREN PHILMORE | | | FIRE INSPECTOR II / INVESTIGATOR I | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4783 | | | |
|