| 2013-08-16 14:49:15 | BUILDING PLAN REVIEW |
| | PERMIT: 13071001 |
| | ADD: 2119 S DIXIE HWY |
| | CONT: TO BE DETERMINED |
| | TEL: (561)312-5921 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: AUGUST 16/2013 |
| | ACTION: DENIED |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) SHEET SP-2.0 INDICATE AT THE (2) ACCESSIBLE PARKING |
| | SPACESFROM THE ACCESS AISLE THERE IS A RAMP TO THE NEW |
| | SIDE WALK, PLEASE PROVIDE A DETAIL OF THIS AREA, |
| | NORMALLY THERE IS A CURB CUT OR CURB RAMP IN COMPLIANCE |
| | WITH 2010 FBC- ACCESSIBILITY CODE 406.1-5. |
| | |
| | 2) SHEET A1.1: |
| | 2A) DISCREPANCIES IN PLANS ON A1.1 FLOOR PLAN, SEE |
| | SECTION LABELED DETAIL A/A6 & B/A6 PLEASE REVERSE |
| | SECTION DETAIL. |
| | DISCREPANCIES IN SECTION TO THE RIGHT OF THE FLOOR PLAN |
| | ARE ALSO LABELED WITH THTE SAME A6 SHEET, SHOULD THEY |
| | BE LABELED A1? |
| | |
| | 2B) WAALL LEGEND FOR WALL TYPES INDICATES AND |
| | ALTERNATIVE WITH THE WORD "OR". WWEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 2010 EDITION, 107.2.1 SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 3) SHEET A6 DETAIL- B INDICATES A SLOPED SCISSOR TYPE |
| | TRUSS WITH A SLOPED BOTTOM CORD, SHEET A8 DETAIL A |
| | INDICATES THE BOTTOM CHORD OF TRUSSES AT TWO DIFFERNT |
| | LEVELS A DISCREPANCY IN DETAILS. PLEASE SEE THE |
| | STRUCTURAL S1 ONLY ONE TYPE OF TRUSS IS INDICATED, NOT |
| | TWO TYPES OF TRUSSES. |
| | |
| | 4A) SHEET A8 DETAIL A INDICATES A DROPED CEILING AND |
| | THE WALL INSULATION ONLY GOING 6 INCHES ABOVE THE |
| | DROPPED CEILING. THIS SHEET ALSO INDICATES THE WALL |
| | INSULATION TYPE TO BE R4.1 FOIL INSULATION. PLEASE |
| | REFER TO THE ENERGY CALCULATIONS AND THE VALUES |
| | PROVIDED THERE SHOW TTHE USE OF .75 INCH ISO INSULATION |
| | BETWEEN THE FURRING STRIPS AT 24 INCHES ON CENTER. |
| | |
| | 4B) THE PLANS DO NOT INDICATE WHERE THE ROOF INSULATION |
| | WILL BE PLACED. IF THE ROOF INSULATION A R-19 BRD |
| | INSULATION (ENERGY CALCULATIONS) IS PLACED AT THE ROOF |
| | LINE, THEN THE END WALL, WALL INSULATION SHOULD |
| | CONTINUE TO THE ROOF TOP INSULATION COMPLETING THE |
| | ENVELOPE SEAL. |
| | |
| | 4C) THE RESTROOM FLOOR PLAN INDICATES A 7'-0" WIDE |
| | RESTROOM , TO HAVE THE 60 INCH CLEARANCE REQUIRED FOR |
| | THE WATER CLOSET REQUIRED FOR THE 2010 FL ACC CODE |
| | 604.3.2 THE MINIMUM CLEARANCE WOULD BE 7'-1". SEE 2010 |
| | FL ACC CODE FIGURE 604.8.1.6. |
| | |
| | 5) SHEET S-0: |
| | 5A) MISSING SOILS REPORT: 2010 FBC-B 1803.5.2 |
| | QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED |
| | |
| | 5B) THE PLANS PROVIDE THE ROOF PRESSURES, PLEASE NOTE |
| | IF THE PRESSURES ARE VULT OR VASD. PLEASE NOT ALL |
| | PRODUCT APPROVALS ARE EXPRESSED IN VASD. |
| | |
| | 5C) THE STRUCTURAL SHEETS DO NOT PROVIDE THE PRESSURES |
| | FOR WINDOWS & DOORS, 2010 FBC-B 1609.6.4.4.1 COMPONENTS |
| | & CLADDING. |
| | |
| | 5D) NEITHER THE A OR S SHEETS INDICATE THE THICKNESS OF |
| | THE ROOF SHEATHING TO BE INSTALLED. |
| | |
| | 6) SHEET S-1 DETAIL 04/S1 MISSING DETAIL? ADDITIONAL |
| | INFORMATION IS REQUIRED. 107.2.1. |
| | |
| | 7) PRODUCT APPROVALS: |
| | 7A) THEMA TRU DOORS, PLEASE PROVIDE COMPLIANCE THAT |
| | THESE DOORS WERE TESTED AND LISTED UNDER THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM, PROVIDE DOCUMENTATION THEY ARE |
| | CURRENT UNDER THE FL 2010 CODE. RULE 9N3 (31)( A). |
| | |
| | 7B) THE TRULITE STOREFRONT GLAZING SYSTEM CG5000S2 |
| | APPEARS TO REFERANCE THE TAS STANDARDS BUT THERE IS NO |
| | MIAMI-DADE TEST REPORT SUBMITTED SHOWING A CURRENT NOA, |
| | THE PRODUCT APPROVAL REPORT WILL BE REQUIRED BEFORE ANY |
| | SHOP DRAWINGS CAN BE REVIEWED FOR CODE COMPLIANCE. RULE |
| | 9N3(31)(B). NOTE A MULLION REPORT MAY ALSO BE REQUIRED |
| | FOR THE HEIGHTS SHOWN ON SHEET A-7. |
| | |
| | 7C) PGT PW 701 FIXED WINDOW, PLEASE HIGHLIGHT (CIRCLE) |
| | IF THIS IS GOING TO BE A FIN AND FLANGED WINDOW AS WELL |
| | AS THE SIZE FOR PRESSURES ON SHEET 2 OF 8. |
| | |
| | 7D) NOA 11-0329.02 IS EXPIRED, SUBMIT A NEW REPORT, |
| | INDICATE THE METHOD OF ANCHORING THE TILE AND MOMENT OF |
| | UPLIFT. PLEASE ALSO PROVIDE THE TYPE OF UNDERLAYMENT TO |
| | BE INSTALLED. |
| | |
| | 7E) UNITREX POLYCARBONATE TRANSLUCENT ROOF- PROVIDE |
| | PRODUCT TESTING FOR THIS SYSTEM THAT IT MEETS THE 170 |
| | MPH 3 SECOND GUST WIND ZONE, 2010 FBC-B 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |