| Notes |
| Date |
Text |
| 2013-07-30 13:52:33 | RE-ROOF, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF OF NOA 12-0716.18 | | | SUBMITTED. THESE CALCULATIONS ARE REQUIRED TO MEET THE | | | DESIGN PRESSURES OF SEC. 1609.4.2 OF 2010 FBC. | | | | | | 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY AND BASE | | | SHEET FASTENING OPTION IS GOING TO BE USED TO VERIFY | | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609.4.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|