| 2013-09-14 16:31:25 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2010 CODE FAMILY W/ 2012 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PAGE M2.1 EXERCISE ROOM 142, TWO OF THE SIX SUPLY |
| | REGISTERS DO NOT SHOW THE DUCTS THAT FEED THEM. PLEASE |
| | CORRECT. FBC-M 603.1. |
| | |
| | 2. PAGE M2.1 FIRE PUMP ROOM 141 WALLS CARRY A 2-HOUR |
| | FIRE RATING. SHOW HOW DUCT PENETRATION OF THIE REATED |
| | WALL IS TO BE PROTECTED PER FBC-M 607.5. |
| | |
| | 3. PAGE M2.1 TERMINATION ROOM 131 WALLS CARRY A 1-HOUR |
| | FIRE RATING. SHOW HOW DUCT PENETRATION OF THIS REATED |
| | WALL IS TO BE PROTECTED PER FBC-M 607.5. |
| | |
| | 4. PAGE M2.1 FIRE ROOM 131 WALLS CARRY A 1-HOUR FIRE |
| | RATING. SHOW HOW DUCT PENETRATION OF THIS REATED WALL |
| | IS TO BE PROTECTED PER FBC-M 607.5. |
| | |
| | 5. PAGE M2.1 PREP ROOM 113 COMMERCIAL KITCHEN GREASE |
| | EXHAUST SYSTEM REQUIRES SEPARATE PLANS AND PERMIT. |
| | |
| | 6. PAGE M2.2 THROUGH M2.6: ALL DUCT PENETRATIONS OF |
| | RATED SHAFT ENCLOSURES SHALL BE PROTECTED WITH FIRE AND |
| | SMOKE DAMPERS PER FBC-M 607.5.5. |
| | |
| | 7. PAGE M2.2 THROUGH M2.6: PENETRATIONS OF RATED |
| | CORRIDOR SHALL BE PROTECTED WITH FIRE AND SMOKE DAMPERS |
| | PER FBC-M 607.5.4. |
| | |
| | 8. PAGE M4.1 PLAN NOTE M18 CALL FOR CONDENSATE TO |
| | DISCHARGE INTO SINK P-TRAP. CONDENSATE SHALL NOT |
| | DISCHARGE INTO SANITARY SYSTEM PER CITY ORDINANCE. |
| | |
| | 9. PAGE M4.1 PLAN NOTE M34 CALLS FOR DOOR UNDERCUT FOR |
| | RETURN AIR. BALANCED RETURN IS REQUIRED IN ALL |
| | HABITABLE ROOMS PER FBC-M 601.4. |
| | |
| | 10. PROVIDE COOLING AND HEATING LOAD CLACULATIONS. |
| | |
| | 11. PROVIDE RATIONAL ANALYSIS FOR SMOKE CONTROL SYSTEM |
| | PER FBC-B 909.4. |
| | |