| 2013-09-19 14:02:18 | #13070994 |
| | 455 HIBISCUS |
| | MARRIOTT RESIDENCE INN |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | E1.1 |
| | PROVIDE A DESIGNATED CLEAR WORKING SPACE AROUND THE |
| | ELECTRICAL SERVICE EQUIPMENT AND PANEL BOARDS. NEC |
| | 215.5, 110.26 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. |
| | NEC 110.22, 110.16, 110.22 |
| | |
| | VERIFY THE FIRE PUMP CIRCUIT CONDUCTORS ARE PROPERLY |
| | PROTECTED. NEC 695.6 |
| | |
| | VERIFY THE FIRE PUMP OVER CURRENT PROTECTIVE DEVICES |
| | HAVE BEEN SELECTED TO CARRY INDEFINITELY THE SUM OF THE |
| | LOCKED-ROTOR CURRENT OF THE FIRE PUMP EQUIPMENT. NEC |
| | 694.4 |
| | |
| | PROVIDE A SIGN AT THE SERVICE-ENTRANCE EQUIPMENT |
| | INDICATING TYPE AND LOCATION OF THE ON-SITE EMERGENCY |
| | POWER SOURCES. NEC 700.8 |
| | |
| | PROVIDE SIGNAGE DETAIL FOR ALL FIRE PUMP DISCONNECTS |
| | AND CONTROLLERS. NEC 695.4 |
| | |
| | VERIFY THE POWER SOURCE SUPPLIED BY THE ON-SITE |
| | GENERATOR TO THE FIRE PUMP CONNECTS TO A DEDICATED |
| | DISCONNECTING MEANS SEPARATE FORM THE OTHER GENERATOR |
| | DISCONNECTING MEANS. NEC 695.4 |
| | |
| | VERIFY THE EMERGENCY CIRCUIT WIRING IS FULLY PROTECTED. |
| | NEC 695.14, 700.9 |
| | |
| | VERIFY THAT ALL WIRING FROM THE EMERGENCY SOURCE HAS |
| | BEEN KEPT ENTIRELY INDEPENDENT OF ALL OTHER WIRING AND |
| | EQUIPMENT INCLUDING CONTROL CONDUCTORS TO THE |
| | GENERATOR. NEC 695.14 700.9(B) |
| | |
| | PROVIDE LISTING AND SPECIFICATIONS ON THE EMERGENCY |
| | ELEVATOR RECALL TRANSFER SWITCH. NEC 110.3 |
| | |
| | PROVIDE A LOAD SUMMARY FOR THE GENERATOR BRANCH WHICH |
| | SUPPORTS ITS SELECTION TO PROVIDE EMERGENCY POWER TO |
| | 'EDP', 'E1' AND THE FIRE PUMP. NEC 215.2, 220.40 |
| | |
| | VERIFY THE GENERATOR HAS DUAL FUEL SUPPLIES. NEC |
| | 700.12(B) |
| | |
| | VERIFY THE EMERGENCY SYSTEM HAS THE CAPACITY TO CONNECT |
| | TO A PORTABLE OR TEMPORARY ALTERNATE SOURCE OF POWER |
| | WHEN THE GENERATOR IS OUT OF SERVICE FOR MAJOR REPAIR. |
| | NEC 700.5 B |
| | |
| | |
| | E1.2 |
| | |
| | FIRE PUMP FEEDER APPEARS TO BE UNDERSIZED BASED ON THE |
| | SELECTED 100 HP FIRE PUMP WITH PRESSURE MAINTENANCE |
| | PUMPS. NEC 695.6 |
| | |
| | VERIFY EQUIPMENT GROUND SELECTION FOR PANEL 'DBP'. NEC |
| | T250.122 |
| | |
| | E1.3 |
| | PROVIDE DETAIL FOR FIRE STOPPING OF ALL FLOOR AND WALL |
| | PENETRATIONS. NEC 300.21 |
| | |
| | E1.4 |
| | CLARIFY PANEL S2 FED FROM DPX ? WHAT IS DPX? |
| | |
| | CLARIFY LOCATION OF PANEL C (100 AMP) NOT SHOWN ON |
| | MSB-B |
| | |
| | VERIFY ELEVATOR PIT AND LIGHT FED FROM PANEL 'L' IS NOT |
| | CONSIDERED AN EMERGENCY LOAD. |
| | |
| | VERIFY THE SUMP PUMP FED FROM PANEL 'L' IS NOT |
| | CONSIDERED AN EMERGENCY LOAD. |
| | |
| | E 2.2 |
| | VERIFY THE FIRE PUMP HAS BEEN LOCATED WITHIN A ROOM |
| | THAT HAS A 2 HOUR RATED FIRE RESISTIVE SEPARATION. FBC |
| | 913.2.1 |
| | |
| | INDICATE THE PROPOSED WIRING METHOD AND CLASSIFICATION |
| | FOR THE POOL EQUIPMENT AREA. NEC 505.5 |
| | |
| | E2.3 |
| | VERIFY THE TRANSFORMER VAULT HAS A 3 HOUR FIRE |
| | RESISTIVE CONSTRUCTION . NEC 450.42 |
| | VERIFY THE ELECTRIC DRINKING FOUNTAIN HAS GFCI |
| | PROTECTION. NEC 422.52 |
| | |
| | E2.5, E2.8, E2.9 |
| | |
| | LIGHTING TIMERS REQUIRE BACKUP PROTECTION. FBC-EC |
| | 505.2.4 |
| | |
| | VERIFY THE LIGHTING SCENES, SEQUENCING AND CONTROLS |
| | MEET THE REQUIREMENTS OF FBC ENERGY CODE. FBC-EC 505.2 |
| | |
| | PROVIDE LIGHTING POWER DENSITY COMPLIANCE CERTIFICATION |
| | ON ELECTRICAL PLANS. FBC-EC 505.503 |
| | |
| | SEPARATE PERMIT WITH PLANS AND WIND LOAD ENGINEERING |
| | FOR POLES WITH LIGHT ASSEMBLY REQUIRED FOR |
| | CONSTRUCTION. FBC 1604.1, ASCE 7/10 |
| | |
| | E3.1 |
| | PROVIDE SAFE WORKING CLEARANCE DETAIL/DIMENSIONS ON |
| | PLANS FOR ALL GUEST ROOM PANEL BOARDS. NEC 110.26 |
| | |
| | E5.1 |
| | PROVIDE A SUMMARY LOAD CALCULATION FOR THE ELECTRICAL |
| | SERVICE, INCLUDING DISTRIBUTION AND GUEST ROOMS. NEC |
| | 230.31 |
| | |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS REQUIRED FOR SWIMMING |
| | POOL, FIRE ALARM SYSTEM, SITE LIGHTING, LOW VOLTAGE |
| | SYSTEMS, ETC. |
| | |