Plan Review Notes
Plan Review Notes For Permit 13070943
Permit Number 13070943
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-08-08 12:48:502501 NORTH AUSTRALIAN AVENUE
 PERMIT #13070943
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS1: THERE APPEARS TO BE OPERABLE KITCHEN DOORS
 AND WINDOWS LOCATED WITHIN 10 FEET BELOW THE GREASE
 EXHAUST FAN. PER NFPA 96 SECTION 7.8.3, "WALL
 TERMINATIONS SHALL BE ARRANGED WITH OR PROVIDED WITH
 THE FOLLOWING PROPERTIES:
 (1) THROUGH A NONCOMBUSTIBLE WALL WITH A MINIMUM OF 10
 FEET OF CLEARANCE FROM THE OUTLET TO ADJACENT
 BUILDINGS, PROPERTY LINES, GRADE LEVEL, COMBUSTIBLE
 CONSTRUCTION, ELECTRICAL EQUIPMENT OR LINES, AND THE
 CLOSEST POINT OF ANY AIR INTAKE OR OPERABLE DOOR OR
 WINDOW AT OR BELOW THE PLANE OF THE EXHAUST
 TERMINATION."
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  