| Plan Review Notes For Permit 13070893 |
| Permit Number |
13070893 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-29 11:31:53 | FBC 2010 EXISTING BUILDING CODE | | | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1.SHEET 7: BUISNESS OCCUPANCIES WITH OVER 15 OCCUPANTS | | | REQUIRE A DRINKING FOUNTAIN. THE ACCESSIBILITY CODE | | | REQUIRES THAT IT IS A HI/LOW DRINKING FOUNTAIN. | | | FBC PLUMBING 403.1 (D, & E) | | | FBC ACCESSIBILITY 211.2 MINIMUM NUMBER. | | | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. | | | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH | | | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH | | | 602.7. | | | | | | | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|