Plan Review Notes
Plan Review Notes For Permit 13070890
Permit Number 13070890
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2013-11-20 13:40:134047 OKEECHOBEE BOULEVARD - SUITE #101
 PERMIT #13070890
 REVIEW COMMENTS - FIRE DEPARTMENT
 ***NOTE: THIS IS A CHANGE OF OCCUPANCY FROM BUSINESS TO
 ASSEMBLY***
  
 MAIN ENTRANCE DOOR: DOORS SERVING AN OCCUPANT LOAD OF
 50 OR MORE PERSONS SHALL SWING IN THE DIRECTION OF
 EGRESS.
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100
 OR MORE PERSONS (50 PERSONS PER THE FLORIDA BUILDING
 CODE), PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO
 RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE
 PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 PROVIDE AN ADDITIONAL EMERGENCY LIGHT FIXTURE NEAR THE
 REAR EXIT DOOR.
  