| Notes |
| Date |
Text |
| 2013-11-20 13:40:13 | 4047 OKEECHOBEE BOULEVARD - SUITE #101 | | | PERMIT #13070890 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | ***NOTE: THIS IS A CHANGE OF OCCUPANCY FROM BUSINESS TO | | | ASSEMBLY*** | | | | | | MAIN ENTRANCE DOOR: DOORS SERVING AN OCCUPANT LOAD OF | | | 50 OR MORE PERSONS SHALL SWING IN THE DIRECTION OF | | | EGRESS. | | | | | | FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 | | | OR MORE PERSONS (50 PERSONS PER THE FLORIDA BUILDING | | | CODE), PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO | | | RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE | | | PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC | | | HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN | | | ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR | | | LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING | | | THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS | | | OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN | | | HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE | | | SUBSTITUTED FOR A KEYED LOCK. | | | | | | PROVIDE AN ADDITIONAL EMERGENCY LIGHT FIXTURE NEAR THE | | | REAR EXIT DOOR. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|