| 2013-11-14 12:56:02 | RETURNED TO BIN B10 FOR FIRE REVIEW | | 2013-11-14 12:55:25 | THIS PERMIT HAS BEEN CONDITIONALLY APPROVED SUBJECT TO | | | THE FOLLOWING CORRECTIONS WHICH WERE PREVIOUSLY | | | MENTIONED BUT NOT ADDRESSED ON RE-SUBMITTAL BEING | | | VERIFIED IN THE FIELD: | | | 1. ALL MULTI-WIRE BRANCH CIRCUITS SHALL COMPLY WITH NEC | | | 210.4 | | | 2. ELECTRICAL NOTE 5 REQUIRES ALL CONDUCTORS TO BE | | | THHN, YET NEC 300.5(B) DICTATES OTHERWISE. THE NEW | | | FEEDER CONDUCTORS SHALL COMPLY ACCORDINGLY | | | | | | |
|