| Notes |
| Date |
Text |
| 2013-08-28 13:15:36 | PLANS DENIED | | | 1) FRESH AIR CALCULATIONS ON PLAN CALL FOR 49 PEOPLE. | | | CUSTOMER SEATING IS 82 REFER TO TABLE403.3 2010 FBC (M) | | | 2) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS | | | FOR FRESH AIR AND EXHAUST. 2010 FLORIDA ENERGY CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|