Plan Review Notes
Plan Review Notes For Permit 13070890
Permit Number 13070890
Review Stop M
Sequence Number 1
Notes
Date Text
2013-08-28 13:15:36PLANS DENIED
 1) FRESH AIR CALCULATIONS ON PLAN CALL FOR 49 PEOPLE.
 CUSTOMER SEATING IS 82 REFER TO TABLE403.3 2010 FBC (M)
 2) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS
 FOR FRESH AIR AND EXHAUST. 2010 FLORIDA ENERGY CODE.