| Plan Review Notes For Permit 13070890 |
| Permit Number |
13070890 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-04 13:04:35 | FIRST REVIEW - 9-4-13 | | | 1. COMPLY TO ARTICLE 505 OF THE FLORIDA ENERGY CODE FOR | | | LIGHTING CONTROLS | | | 2. PROVIDE LIGHTING CONTROL FOR MEZZ LIGHTING. NONE | | | SHOWN | | | 3. ALL 15/20 AMP, 120V RECEPTS IN KITCHEN TO BE GFCI | | | TYPE. ADD NOTE | | | 4. CONDUCTORS UNDERGROUND OR IN SLAB, WHETHER IN | | | CONDUIT OR NOT, SHALL COMPLY TO NEC 300.5B FOR WWET | | | LOCATION | | | 5. MULTI BRANCH CIRCUITS SHALL COMPLT TO NEC 210.4. ADD | | | NOTE | | | END OF REVIEW - VB |
|