2013-08-14 15:34:28BUILDING PLAN REVIEW
 PERMIT: 13070890
 ADD: 4047 OKEECHOBEE BLVD # 101
 CONT: BTD CONTRACTING LLC
 TEL: (904)707-7919
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 14/ 2013
 ACTION: DENIED
  
 1) SHEET 1.1:
 1A) THE TITLE BLOCK INDICATES THAT AMES BENNETT TO BE
 THE DESIGNER OF RECORD FL S 481. ACROSS THE BOTTOM OF
 THE SHEET, THE ADVERTIEMENT: CAD DESIGN AND DRAFTING BY
 ANDREW SLACK, WHO IS THE DESIGNER?
  
 1B) UNDER THE HEAING PROJECT DATA, THE PLANS INDICATE
 THIS TO BE A LEVEL II ALTERATION. THIS TENANT SPACE IS
 GOING FROM A MERCANTILE OCCUPANCY TO AN A2 ASSEMBLY
 OCCUPANCY NOT A A3. SEE 2010 FBC-B 303.1.
  
 1C) WITH THERE BEING A CHANGE OF OCCUPANCY, THE LELVEL
 OF ALTERATION CHANGES, SEE 2010 FL EXISTING BUILDING
 CODE CHAPTER 9 SECTION 901.3.1. 2010 FL EXST BLDG CODE
 901.3.1 PARTIAL CHANGE OF OCCUPANCY
 CLASSIFICATION.WHERE A PORTION OF AN EXISTING BUILDING
 IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION
 912 SHALL APPLY.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1D) THE PLANS INDICATE THE INSTALATION OF A NEW
 MEZZANINE LEVEL. PLEASE SHOW COMPLIANCE WITH 2010 FBC-
 EXIST BLDG 907.1 GRAVITY LOADS.
 BUILDINGS OR PORTIONS THEREOF SUBJECT TO A CHANGE OF
 OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY
 RESULTS IN HIGHER UNIFORM OR CONCENTRATED LOADS BASED
 ON THE FLORIDA BUILDING CODE, BUILDING TABLES 1607.1
 AND 1607.6 SHALL COMPLY WITH THE GRAVITY LOAD
 PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING. AT
 WHAT LIVE LOADING IS THE MEZZANINE LEVEL TO BE DESINED
 TOO? 2010 FBC-B TABLE 1607.1( 36 OR 37).
  
 1E) DETAIL WALL SECTIONS 2 & 3 BOTH SHOW THE USE OF
 INBEDS AND NELSON BOLTS, AREN'T NELSON BOLTS USED ON
 NEW CONCRETE BEAMS NOT EXISTING CONCRETE BEAMS?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 1F) PLEASE PROVIDE A CUT SECTION THROUGH THE KITCHEN/
 MEZZANINE LEVEL PLEASE PROVIDE THE CLEAR HEIGHTS OF THE
 KITCHEN AND MEZZANINE LEVEL PER 2010 FBC-B 1208.2
 MINIMUM CEILING HEIGHTHS.
  
 2) SHEET 1.2:
 2A) GENERAL NOTES PLEASE UPDATE NOTES 1,7,18,22 & 23
 ALL DEAL WITH LOCAL CODES OR AMENDMENTS TO THE
 TECHNICAL CODE. THE 2010 FBC ONLY ALLOWS LOCAL
 AMENDMENTS TO CHAPTER 1 ADMINISTRATION, THERE ARE NO
 LOCAL TECHNICAL AMENDMENTS SINCE THE 2004 FBC.
  
 2B) NOTES BY EQUIPMENT LABELED #112 INDICATE COMPLIANCE
 WITH 11-42 & FIGURE 54 FBC-10. PLEASE UPDATE REFERANCES
 TO THE FL ACCESSIBILITY CODE, THERE IS NO LONGER A
 CHAPTER 11 IT IS A SEPERATE BOOK THAT IS FORMATED TO
 THE NEW 2010 ADA CODE SECTION, FLORIDA CODE IS IN THE
 GRAY BOXES.
  
 2C) THE PLANS INDICATE THE FRONT DOOR BEING REVERSED.
 PLEASE SHOW PRODUCT APPROVAL FOR THIS DOOR BEING TESTED
 IN THE REVERSE POSITION FOR WIND. 2010 FBC-B
 1609.6.4.4.1. COMPONENTS AND CLADDING.
  
 2D) THE RESTROOM DOORS SWING OUT INTO THE PATH OF
 EGRESS, THE MENS RESTROOM DOOR BLOCKS THE REAR EXIT.
 2010 FBC-B 1008.1.1.1 PROJECTIONS INTO CLEAR WIDTH.
  
 2E) PLEASE BE AWARE THAT THE RESTROOM DOORS CAN SWING
 INTO THE RESTROOM. PLEASE SEE 2010 FBC-ACCESSIBLITY
 CODE 603.2.3 EXCEPTION # 2 AND ADA DIAGRAMS THAT
 CORESPONDS TO THE FL EXCEPTION # 2, FLORIDA DOES NOT
 SHOW IT IN THE FL ACCESSIBLITY CODE BOOK.
  
 2F) THE KITCHEN DOOR THAT LEADS INTO THE COORIDOR
 OPOSITE OF THE RESTROOMS SHOULD SWING 180 DEGREES. SEE
 2010 FBC-B 1005.2 OR 1008.1.9.11 THE CORRIDOR IS 5'-0"
 WIDE OR 60 INCHES. THE REQUIRED CORRIDOR WIDTH IS 44"
 THE DOOR SWING IS 36 INCHES, 1/2 OF THE REQUIRED
 CORRIDOR WIDTH OF 22 INCHES, 22 +36= 58 INCHES, IT
 MEETS THE WIDTH REQUIREMENT BUT NEEDS TO BE ON 180
 DEGREE HINGES SO IT WILL NOT PROJECT MORE THAN 7 INCHES
 INTO THE CORRIDOR. JUST A POSSIBLE SOLUTION.
  
 2G) NOTE ON PLANS INDICATES ENCLOSED STEEL STAIRS
 SUBMIT SHOP DRAWING BY OTHERS, PLEASE PROVIDE A DESIGN
 CRITERIA FOR LIVE LOADS 2010 FBC-TABLE 1607.1(35).
  
 3) SHEET 2.1:
 3A) THE PLANS INDICATE MEANS OF EGRESS, PLEASE PROVIDE
 THE REQUIRED CLEAR WIDTH ON THE PLAN, THE PLANS WILL
 ALSO NEED TO SHOW COMPLIANCE WITH 2010 FBC-B 1017.4.3
 TABLE AND SEATING AISLE ACCESSWAY LENGTH.
 THE LENGTH OF TRAVEL ALONG THE AISLE ACCESSWAY SHALL
 NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT
 WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF
 EGRESS TRAVEL TO SEPARATE EXITS. IT APPEARS THE FIRST
 ROW OF 4 TABLES WILL MEET THIS REQUIREMENT BUT NOT THE
 OTHER ROWS.
  
 3B) PLEASE ALSO INCLUDE THE LINE OF PEOPLE THAT ARE
 BEING HELPED AT THE FRONT COUNTER, THIS AREA APPEARS TO
 BE TIGHT FOR MEANS OF EGRESS.
 2010 FBC-B 1018.2 44 INCHES.
  
 3C) SHEET 3.2:
 3A) THE REGISTER SYSTEM IS INDICATED TO BE 4'-4" TALL,
 PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-ACCESSIBILITY
 CODE 904.3.2 & 904.3.3.
  
 3B) PLEASE ALSSO SHOW COMPLIANCE WITH 2010 FL
 ACCESSIBILITY CODE 904.5 (1, 2 &6).
  
 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved