| Date |
Text |
| 2013-08-14 15:34:28 | BUILDING PLAN REVIEW |
| | PERMIT: 13070890 |
| | ADD: 4047 OKEECHOBEE BLVD # 101 |
| | CONT: BTD CONTRACTING LLC |
| | TEL: (904)707-7919 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: AUGUST 14/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET 1.1: |
| | 1A) THE TITLE BLOCK INDICATES THAT AMES BENNETT TO BE |
| | THE DESIGNER OF RECORD FL S 481. ACROSS THE BOTTOM OF |
| | THE SHEET, THE ADVERTIEMENT: CAD DESIGN AND DRAFTING BY |
| | ANDREW SLACK, WHO IS THE DESIGNER? |
| | |
| | 1B) UNDER THE HEAING PROJECT DATA, THE PLANS INDICATE |
| | THIS TO BE A LEVEL II ALTERATION. THIS TENANT SPACE IS |
| | GOING FROM A MERCANTILE OCCUPANCY TO AN A2 ASSEMBLY |
| | OCCUPANCY NOT A A3. SEE 2010 FBC-B 303.1. |
| | |
| | 1C) WITH THERE BEING A CHANGE OF OCCUPANCY, THE LELVEL |
| | OF ALTERATION CHANGES, SEE 2010 FL EXISTING BUILDING |
| | CODE CHAPTER 9 SECTION 901.3.1. 2010 FL EXST BLDG CODE |
| | 901.3.1 PARTIAL CHANGE OF OCCUPANCY |
| | CLASSIFICATION.WHERE A PORTION OF AN EXISTING BUILDING |
| | IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION |
| | 912 SHALL APPLY. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1D) THE PLANS INDICATE THE INSTALATION OF A NEW |
| | MEZZANINE LEVEL. PLEASE SHOW COMPLIANCE WITH 2010 FBC- |
| | EXIST BLDG 907.1 GRAVITY LOADS. |
| | BUILDINGS OR PORTIONS THEREOF SUBJECT TO A CHANGE OF |
| | OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY |
| | RESULTS IN HIGHER UNIFORM OR CONCENTRATED LOADS BASED |
| | ON THE FLORIDA BUILDING CODE, BUILDING TABLES 1607.1 |
| | AND 1607.6 SHALL COMPLY WITH THE GRAVITY LOAD |
| | PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING. AT |
| | WHAT LIVE LOADING IS THE MEZZANINE LEVEL TO BE DESINED |
| | TOO? 2010 FBC-B TABLE 1607.1( 36 OR 37). |
| | |
| | 1E) DETAIL WALL SECTIONS 2 & 3 BOTH SHOW THE USE OF |
| | INBEDS AND NELSON BOLTS, AREN'T NELSON BOLTS USED ON |
| | NEW CONCRETE BEAMS NOT EXISTING CONCRETE BEAMS? |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 1F) PLEASE PROVIDE A CUT SECTION THROUGH THE KITCHEN/ |
| | MEZZANINE LEVEL PLEASE PROVIDE THE CLEAR HEIGHTS OF THE |
| | KITCHEN AND MEZZANINE LEVEL PER 2010 FBC-B 1208.2 |
| | MINIMUM CEILING HEIGHTHS. |
| | |
| | 2) SHEET 1.2: |
| | 2A) GENERAL NOTES PLEASE UPDATE NOTES 1,7,18,22 & 23 |
| | ALL DEAL WITH LOCAL CODES OR AMENDMENTS TO THE |
| | TECHNICAL CODE. THE 2010 FBC ONLY ALLOWS LOCAL |
| | AMENDMENTS TO CHAPTER 1 ADMINISTRATION, THERE ARE NO |
| | LOCAL TECHNICAL AMENDMENTS SINCE THE 2004 FBC. |
| | |
| | 2B) NOTES BY EQUIPMENT LABELED #112 INDICATE COMPLIANCE |
| | WITH 11-42 & FIGURE 54 FBC-10. PLEASE UPDATE REFERANCES |
| | TO THE FL ACCESSIBILITY CODE, THERE IS NO LONGER A |
| | CHAPTER 11 IT IS A SEPERATE BOOK THAT IS FORMATED TO |
| | THE NEW 2010 ADA CODE SECTION, FLORIDA CODE IS IN THE |
| | GRAY BOXES. |
| | |
| | 2C) THE PLANS INDICATE THE FRONT DOOR BEING REVERSED. |
| | PLEASE SHOW PRODUCT APPROVAL FOR THIS DOOR BEING TESTED |
| | IN THE REVERSE POSITION FOR WIND. 2010 FBC-B |
| | 1609.6.4.4.1. COMPONENTS AND CLADDING. |
| | |
| | 2D) THE RESTROOM DOORS SWING OUT INTO THE PATH OF |
| | EGRESS, THE MENS RESTROOM DOOR BLOCKS THE REAR EXIT. |
| | 2010 FBC-B 1008.1.1.1 PROJECTIONS INTO CLEAR WIDTH. |
| | |
| | 2E) PLEASE BE AWARE THAT THE RESTROOM DOORS CAN SWING |
| | INTO THE RESTROOM. PLEASE SEE 2010 FBC-ACCESSIBLITY |
| | CODE 603.2.3 EXCEPTION # 2 AND ADA DIAGRAMS THAT |
| | CORESPONDS TO THE FL EXCEPTION # 2, FLORIDA DOES NOT |
| | SHOW IT IN THE FL ACCESSIBLITY CODE BOOK. |
| | |
| | 2F) THE KITCHEN DOOR THAT LEADS INTO THE COORIDOR |
| | OPOSITE OF THE RESTROOMS SHOULD SWING 180 DEGREES. SEE |
| | 2010 FBC-B 1005.2 OR 1008.1.9.11 THE CORRIDOR IS 5'-0" |
| | WIDE OR 60 INCHES. THE REQUIRED CORRIDOR WIDTH IS 44" |
| | THE DOOR SWING IS 36 INCHES, 1/2 OF THE REQUIRED |
| | CORRIDOR WIDTH OF 22 INCHES, 22 +36= 58 INCHES, IT |
| | MEETS THE WIDTH REQUIREMENT BUT NEEDS TO BE ON 180 |
| | DEGREE HINGES SO IT WILL NOT PROJECT MORE THAN 7 INCHES |
| | INTO THE CORRIDOR. JUST A POSSIBLE SOLUTION. |
| | |
| | 2G) NOTE ON PLANS INDICATES ENCLOSED STEEL STAIRS |
| | SUBMIT SHOP DRAWING BY OTHERS, PLEASE PROVIDE A DESIGN |
| | CRITERIA FOR LIVE LOADS 2010 FBC-TABLE 1607.1(35). |
| | |
| | 3) SHEET 2.1: |
| | 3A) THE PLANS INDICATE MEANS OF EGRESS, PLEASE PROVIDE |
| | THE REQUIRED CLEAR WIDTH ON THE PLAN, THE PLANS WILL |
| | ALSO NEED TO SHOW COMPLIANCE WITH 2010 FBC-B 1017.4.3 |
| | TABLE AND SEATING AISLE ACCESSWAY LENGTH. |
| | THE LENGTH OF TRAVEL ALONG THE AISLE ACCESSWAY SHALL |
| | NOT EXCEED 30 FEET (9144 MM) FROM ANY SEAT TO THE POINT |
| | WHERE A PERSON HAS A CHOICE OF TWO OR MORE PATHS OF |
| | EGRESS TRAVEL TO SEPARATE EXITS. IT APPEARS THE FIRST |
| | ROW OF 4 TABLES WILL MEET THIS REQUIREMENT BUT NOT THE |
| | OTHER ROWS. |
| | |
| | 3B) PLEASE ALSO INCLUDE THE LINE OF PEOPLE THAT ARE |
| | BEING HELPED AT THE FRONT COUNTER, THIS AREA APPEARS TO |
| | BE TIGHT FOR MEANS OF EGRESS. |
| | 2010 FBC-B 1018.2 44 INCHES. |
| | |
| | 3C) SHEET 3.2: |
| | 3A) THE REGISTER SYSTEM IS INDICATED TO BE 4'-4" TALL, |
| | PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-ACCESSIBILITY |
| | CODE 904.3.2 & 904.3.3. |
| | |
| | 3B) PLEASE ALSSO SHOW COMPLIANCE WITH 2010 FL |
| | ACCESSIBILITY CODE 904.5 (1, 2 &6). |
| | |
| | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |