| 2013-07-27 11:40:35 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ENHANCED FASTENING SPECIFIED BY AN ARCHITECT, | | | ENGINEER, OR REGISTERED ROOF CONSULTANT REQUIRED AS THE | | | ASSEMBLY SELECTED DOES NOT MEET MINIMUM DESIGN | | | PRESSURES FOR ALL ZONES, FBC 2010 RESIDENTIAL 301. SEE | | | GENERAL LIMITATION #7 ON THE LAST PAGE OF THE NOA. | | | | | | 2. TWO SETS OF PLANS REQUIRED FBC 107. FAILURE TO | | | PROVIDE TWO SETS WILL RESULT IN ADMIN/COPY FEES. | | | | | | |
|