2013-08-17 13:46:00BUILDING PLAN REVIEW
 PERMIT:13070828
 ADD: 1741 PALM BEACH LAKES BLVD SUITE # ???????
 CONT:TO BE DETERMINED
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SATURDAY AUGUST 17/2013
 ACTION: DENIED
  
 1) THE PLANS NOR PERMIT APPLICATION PROVIDE THE SUITE #
 WHERE WORK IS TO BE COMPLETED UNDER THIS PERMIT. 2010
 FBC 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 3) 0013/ SHEET A6.1 DETAIL #9 HIGH LOW DRINKING
 FOUNTAINS, PLEASE BE AWARE THAT THE HIGH SIDE DRINKING
 FOUNTAIN DOES NOT INDICATE THE VERTICAL CLEARANCE
 BENEATH WHERE BASIN PORTION OF THE UNIT, COMMONLY IT
 DOES NOT MEET SECTION 2010 FBC ACCESSIBILITY CODE:
 2010 FL ACCESSIBILITY CODE AT DRINKING FOUNTAIN THE
 UPPER DRINKING FOUNTAIN WILL TO COMPLY WITH
 2010 FL ACCESSIBILITY CODE 307.2 OBJECTS WITH LEADING
 EDGES MORE THAN 27 INCHES (685 MM) AND NOT MORE THAN 80
 INCHES (2030 MM) ABOVE THE FINISH FLOOR OR GROUND SHALL
 PROTRUDE 4 INCHES (100 MM) MAXIMUM HORIZONTALLY INTO
 THE CIRCULATION PATH.
  
 ADVISORY 307.2 PROTRUSION LIMITS.
 WHEN A CANE IS USED AND THE ELEMENT IS IN THE
 DETECTABLE RANGE, IT GIVES A PERSON SUFFICIENT TIME TO
 DETECT THE ELEMENT WITH THE CANE BEFORE THERE IS BODY
 CONTACT. ELEMENTS LOCATED ON CIRCULATION PATHS,
 INCLUDING OPERABLE ELEMENTS, MUST COMPLY WITH
 REQUIREMENTS FOR PROTRUDING OBJECTS.
  
 4) 0015/ SHEET A7.1 THE ACCESSIBLE DRESSING ROOM PLEASE
 REVIEW THE REQUIREMENTS FOR A BACK SUPPORT ON THE
 BENCH.
 2010 FBC- ACCESSIBILITY CODE 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
  
 ADVISORY 903.4 BACK SUPPORT.
 TO ASSIST IN TRANSFERRING TO THE BENCH, CONSIDER
 PROVIDING GRAB BARS ON A WALL ADJACENT TO THE BENCH,
 BUT NOT ON THE SEAT BACK. IF PROVIDED, GRAB BARS CANNOT
 OBSTRUCT TRANSFER TO THE BENCH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved