| 2013-09-18 16:27:01 | 846 SOUTHERN BOULEVARD |
| | PERMIT #13070820 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| | EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| | BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| | ORDERED FROM WWW.KNOXBOX.COM. |
| | |
| | GENERAL: ALL CONSTRUCTION AND DEMOLITION WORK SHALL |
| | CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH AND |
| | CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED |
| | EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION |
| | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE |
| | SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING |
| | MATERIALS SHALL BE PROVIDED. |
| | |
| | GENERAL: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| | DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| | EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| | MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| | SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| | REQUESTS MUST BE SUBMITTED BY EMAIL ([email protected]) OR |
| | IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE |
| | OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE |
| | HIGHWAY. |
| | |
| | GENERAL: SHELVING AND STORAGE SHALL NOT EXCEED 12 FEET |
| | IN HEIGHT; OTHERWISE, THE DESIGN SHALL MEET THE FIRE |
| | AND LIFE SAFETY REQUIREMENTS FOR "HIGH-PILED STORAGE." |
| | |
| | SHEET A-1 (DOOR #8): PER SECTION 7.2.1.9.1.3 - POWER |
| | OPERATED DOORS: THE POWERED SLIDING DOOR ASSEMBLY SHALL |
| | BE DESIGNED AND INSTALLED SO THAT, WHEN A FORCE IS |
| | APPLIED TO THE DOOR LEAF ON THE SIDE FROM WHICH EGRESS |
| | IS MADE, IT SHALL BE CAPABLE OF SWINGING FROM ANY |
| | POSITION TO PROVIDE FULL USE OF THE REQUIRED WIDTH OF |
| | THE OPENING IN WHICH IT IS INSTALLED. A READILY |
| | VISIBLE, DURABLE SIGN IN LETTERS NOT LESS THAN 1-INCH |
| | HIGH ON A CONTRASTING BACKGROUND THAT READS AS FOLLOWS |
| | SHALL BE LOCATED ON THE EGRESS SIDE OF EACH DOOR |
| | OPENING: IN EMERGENCY, PUSH TO OPEN. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY |
| | EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL |
| | EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED |
| | WITH RESPECT TO THEIR DUTIES UNDER THE PLAN. |
| | |
| | EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED |
| | IN THE USE OF PORTABLE FIRE EXTINGUISHERS. |
| | |