2013-10-27 10:56:58BUILDING PLAN REVIEW
 PERMIT: 13070818
 ADD: 1807 PALM BEACH LAKES
 CONT: HALEY CONSTRUCTION, INC
 TEL: (386)566-7437
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUNDAY OCT. 27/ 2012
 ACTION: BUILDING PROVISO:
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET S4.1 DETAIL # 2 THE CLEAR VERTICAL SPACE UNDER
 A/C CONDENSER STANDS IS TAKEN FROM FINISH ROOF TO THE
 BOTTOM HORIZONTAL FRAMING MEMBER OF THE STAND.
 VERTICAL CLEARANCE IS TO COMPLY WITH THE 2010 FBC-B
 TABLE 1509.7
  
 2) ROOF PRODUCT APPROVAL:
 FL 10128-R4
 FIRESTONE SINGLE PLY SYSTEM
 SUB-SYSTEMS NOT IDENTIFIED, WILL REQUIRE A SEPARATE
 ROOFING PERMIT, REVIEW & ASSOCIATED FEES!!!
  
 3) REVISION REQUIRED:
 NOA 09-0122.01 - EXPIRED
 KD WINDOWS/ HORIZONTAL SLIDERS
 NON-IMPACT
  
 4) REVISION REQUIRED:
 FL812-R5
 ARMOUR SCREEN
 SYSTEM NOT IDENTIFIED AS TO INSTALLATION LOCATION,
 SYSTEM TYPE APPLICATION NOT IDENTIFIED, WIDTH & HEIGHT
 OF OPENING, FASTENRES NOR PRESSURES ASSOCIATED WITH
 OPENING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]