| 2013-10-27 10:56:58 | BUILDING PLAN REVIEW |
| | PERMIT: 13070818 |
| | ADD: 1807 PALM BEACH LAKES |
| | CONT: HALEY CONSTRUCTION, INC |
| | TEL: (386)566-7437 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: SUNDAY OCT. 27/ 2012 |
| | ACTION: BUILDING PROVISO: |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET S4.1 DETAIL # 2 THE CLEAR VERTICAL SPACE UNDER |
| | A/C CONDENSER STANDS IS TAKEN FROM FINISH ROOF TO THE |
| | BOTTOM HORIZONTAL FRAMING MEMBER OF THE STAND. |
| | VERTICAL CLEARANCE IS TO COMPLY WITH THE 2010 FBC-B |
| | TABLE 1509.7 |
| | |
| | 2) ROOF PRODUCT APPROVAL: |
| | FL 10128-R4 |
| | FIRESTONE SINGLE PLY SYSTEM |
| | SUB-SYSTEMS NOT IDENTIFIED, WILL REQUIRE A SEPARATE |
| | ROOFING PERMIT, REVIEW & ASSOCIATED FEES!!! |
| | |
| | 3) REVISION REQUIRED: |
| | NOA 09-0122.01 - EXPIRED |
| | KD WINDOWS/ HORIZONTAL SLIDERS |
| | NON-IMPACT |
| | |
| | 4) REVISION REQUIRED: |
| | FL812-R5 |
| | ARMOUR SCREEN |
| | SYSTEM NOT IDENTIFIED AS TO INSTALLATION LOCATION, |
| | SYSTEM TYPE APPLICATION NOT IDENTIFIED, WIDTH & HEIGHT |
| | OF OPENING, FASTENRES NOR PRESSURES ASSOCIATED WITH |
| | OPENING. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |