| 2013-10-17 17:35:49 | BUILDING PLAN REVIEW |
| | PERMIT: 13070818 |
| | ADD: 1807 PALM BEACH LAKES |
| | CONT: HALEY CONSTRUCTION, INC |
| | TEL: (386)566-7437 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: OCT. 17/ 2012 |
| | ACTION: DENIED |
| | |
| | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE AND REPLACE ANY PAGES AS |
| | NECESSARY. DO NOT LEAVE THE VOID SHEETS INTHE SET!!!!! |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1A) PLEASE CORRECT THE ADDRESS ON BOTH THE PERMIT |
| | APPLICATION AND PLANS FOR ALL TRADES. THE PERMIT |
| | APPLICATION READS 1801 PALM BEACH LAKES WHICH WAS THE |
| | OVER ALL SITE ADDRESS, AND THE PLANS INDICATE A |
| | ADDRESSS OF 1721 WHICH IS ASSIGNED TO BUILDINF J-6 OF |
| | THE PLAM BEACH OUTLETMALL, THE 1721 ADDRESS ALSO HAD |
| | BEEN ASSIGNED TO THE OVERALL SITE ADRESS BUT WENT TO |
| | BEING THE ADDRESS FOR BUILDING J6. SHEET C-3 INDICATES |
| | THE LOCATION OF THE BUILDING AS A OUT PARCEL LOCATED AT |
| | THE SITE 1721 PALM BEACH LAKES. ALL SHEETS WILL NEED TO |
| | BE CORRECTED TO 1807 PALM BEACH LAKES BLVD!!!!!! |
| | |
| | 1B) COMPLIED. CALCULATED VALUETHE PERMIT APPLICATION |
| | INDICATES A VALUE OF $500,000.00. CALCULATED VALUE OF |
| | PROJECT IS $960,000.00. |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 1C) PROJECTS LOCATED AT THE PALM BEACH OUTLET MALL |
| | REQUIRE THE PLANS TO BE STAMPED REVIEWED BY PALM BEACH |
| | OUTLET MALL. |
| | |
| | 2) 2ND REQUEST. THE ARCHITECTURAL SHEETS ARE SIGNED BY |
| | RUBBER STAMP NOT AN ORIGINAL SIGNATURE. PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY |
| | THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN |
| | PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN CODE |
| | 61G16.003 ARCHITECTS |
| | |
| | 3) COMPLIED. |
| | |
| | 4) 2ND REQUEST, SHEET S0.0 UNDER THE HEADING OF SPECIAL |
| | INSPECTION NOTES INDICATES THE OWNER TO PROVIDE A |
| | RESIDENT INSPECTOR TO OVERSEE THE STRUCTURAL JOBSITE |
| | INSPECTIONS.AMENDMENT TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, ADMINISTRATION, 2010 EDITION, WEST PALM |
| | BEACH 110.3.9 THE BUILDING OFFICIAL MAY MAKE, OR CAUSE |
| | TO BE MADE |
| | BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. |
| | HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED |
| | INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION |
| | HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND |
| | RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION |
| | OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH |
| | REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY |
| | A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| | INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| | OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| | THE RESIDENT INSPECTOR. |
| | |
| | AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT, |
| | SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF |
| | COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE |
| | WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN |
| | ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION |
| | SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A |
| | CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION |
| | IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT |
| | ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS. |
| | |
| | PLEASE CONTACT KEN CONRAD THE MANAGER OF THE RESIDENT |
| | INSPECTOR PROGRAM FOR REQUIREMENTS AND DOCUMENTS THAT |
| | MUST BE SUBMITTED FOR A RESIDENT INSPECTOR TO BE |
| | APPROVED WITHIN THE CITY OF WEST PALM BEACH. CONTACT |
| | INFO; |
| | KEN CONRAD CHIEF BUILDING INSPECTOR |
| | TEL: 561-805-6666 |
| | FAX: 561-805- 6676 |
| | E-MAIL: KCONRAD @WPB.ORG |
| | |
| | 5) 2ND REQUEST, ONLY 2 SETS SUBMITTED.PLEASE SUBMIT 3 |
| | SETS OF PLANS AND PRODUCT APPROVALS (STRUCTURAL & |
| | ACHITECTURAL) FOR THE RESIDENT INSPECTOR, 1 SET FOR THE |
| | CONTRACTOR, ONE SET FOR THE RESIDENT INSPECTOR AND THE |
| | THIRD WILL BE THE OFFICE FILE SET. |
| | |
| | 6) 2ND REQUEST. MISSING SOILS REPORT 2010 FBC-B |
| | 1803.5.2 QUESTIONABLE SOILS. |
| | 1803.6 REPORTING. |
| | WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A |
| | WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED |
| | TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED |
| | AGENT AT THE TIME OF PERMIT APPLICATION. THIS |
| | GEOTECHNICAL REPORT SHALL INCLUDE, BUT NEED NOT BE |
| | LIMITED TO, THE FOLLOWING INFORMATION: |
| | 6.1. A PLOT SHOWING THE LOCATION OF THE SOIL |
| | INVESTIGATIONS. |
| | 6.2. A COMPLETE RECORD OF THE SOIL BORING AND |
| | PENETRATION TEST LOGS AND SOIL SAMPLES. |
| | 6.3. A RECORD OF THE SOIL PROFILE. |
| | 6.4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED. |
| | 6.5. RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN |
| | CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING |
| | CAPACITY OF NATURAL OR COMPACTED SOIL; PROVISIONS TO |
| | MITIGATE THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF |
| | THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT |
| | AND VARYING SOIL STRENGTH; AND THE EFFECTS OF ADJACENT |
| | LOADS. |
| | 6.6. EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT. |
| | |
| | 7-9) COMPLIED. |
| | |
| | 10) 2ND REQUEST. SHEET A0.1 & A0.1A IS ANSI 117.1, |
| | PLEASE REFER TO THE 2010 FBC-ACCESSIBILITY CODE. |
| | FLORIDA STATUTE 553.80 PROVIDES FOR THE ENFORCEMENT |
| | OF THIS PART OF THE CODE, THE DEPARTMEENT OF JUSTICE |
| | HAS CERTIFIED THIS CODE. |
| | |
| | 11-14) COMPLIED. |
| | |
| | 15) 2ND REQUEST, SEMI-COMPLIED. SHEET S4.0: |
| | 15A) SEMI-COMPLIED. SHEET A3.1 ROOF TOP ELEVATION OF |
| | 34'-0"/ PARAPET AT 35'-0". |
| | |
| | 15B) COMPLIED. |
| | |
| | 15C) COMPLIED. |
| | |
| | 15D) 2ND REQUEST. ROOF PRESSURES FOR ROOF ZONE # 3 ARE |
| | TAKEN AS THE SAME FOR ROOF ZONE # 2, WHICH IS CORRECT |
| | WHEN THERE IS A ROOF PARPET OF AT LEASRT 3'-0" TALL. |
| | PLEASE REFER TO SHEET A3.1 WHERE THE ROOF TOP ELEVATION |
| | IS 34'-0". |
| | |
| | 16) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 17) 2ND REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING, NO PRODUCT |
| | APPROVALS SUBMITTED THIS REVIEW, RESONSE SHEET |
| | INDICATES PROVIDED??? |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 18) 2ND REQUEST,, SHEET S4.1 A/C STANDS (RACKS, NOT |
| | CURBS) ARE TO COMPLY WITH 2010 FBC-B 1509.7 MECHANICAL |
| | UNITS. THE VERTICAL CLEAR DIMENSION FOR A/C CONDENSORS |
| | ON THE ROOF IS FROM THE BOTTOM OF THE RACK FRAMING |
| | MEMBERS TO FINISH ROOF NOT THE STEEL STRUCTURAL DECK. |
| | ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS |
| | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF |
| | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE |
| | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM |
| | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7. |
| | |
| | 19) COMPLIED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |