| 2013-08-12 15:57:01 | FBC 2010 ACCESSIBILITY CODE |
| | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. WITH AN AGGREGATE OF 6 OR MORE WATER CLOSETS A |
| | UNISEX RESTROOM WILL BE REQUIRED. THE FIXTURES IN THE |
| | UNISEX RESTROOM CAN BE USED IN THE FIXTURE COUNT FOR |
| | MEN OR WOMEN. |
| | 403.5 UNISEX TOILET AND BATHING ROOMS. |
| | IN ASSEMBLY AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE |
| | UNISEX TOILET ROOM SHALL BE PROVIDED WHERE AN AGGREGATE |
| | OF SIX OR MORE MALE AND FEMALE WATER CLOSETS IS |
| | REQUIRED. IN BUILDINGS OF MIXED OCCUPANCY, ONLY THOSE |
| | WATER CLOSETS REQUIRED FOR THE ASSEMBLY OR MERCANTILE |
| | OCCUPANCY SHALL BE USED TO DETERMINE THE UNISEX TOILET |
| | ROOM REQUIREMENT. IN RECREATIONAL FACILITIES WHERE |
| | SEPARATE-SEX BATHING ROOMS ARE PROVIDED, AN ACCESSIBLE |
| | UNISEX BATHING ROOM SHALL BE PROVIDED. FIXTURES LOCATED |
| | WITHIN UNISEX TOILET AND BATHING ROOMS SHALL BE |
| | INCLUDED IN DETERMINING THE NUMBER OF FIXTURES PROVIDED |
| | IN AN OCCUPANCY. |
| | |
| | 2. SHEET P1.2 & P2.1 ALL HOSE BIBBS REQUIRE SEPARATE |
| | SHUTOFF VALVES. |
| | 606.2 LOCATION OF SHUTOFF VALVES. |
| | SHUTOFF VALVES SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 2. ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER |
| | THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| | |
| | 3. SHEET 4.0 DETAIL #11 SHOWS AC CONDENSATE CONNECTED |
| | TO A LAVATORY. AC CONDENSATE IS NOT PERMITTED IN THE |
| | CITY OF WEST PALM BEACH SEWER SYSTEM. |
| | CITY ORD.SEC. 90-126. - PROHIBITIONS AND LIMITATIONS OF |
| | DISCHARGE. (5) |
| | |