2013-09-03 15:17:04PLANS DENIED
 REFER TO SECTION 301.12 WIND RESISTANCE .
 1) PROVIDE A DETAIL ON THE PLAN BY THE ENGINEER
 ON CURB TO ROOF TIEDOWN AND RTU TO CURB
 TIEDOWN. 2010 FBC (M)
 2) SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR
 HOODS WALK IN COOLERS AND FREEZERS