| 2013-07-30 17:42:43 | 1801 PALM BEACH LAKES BOULEVARD |
| | PERMIT #13070818 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: THE ADDRESS OF 1721 PALM BEACH LAKES BOULEVARD |
| | APPEARS TO HAVE ALREADY BEEN ASSIGNED ANOTHER MALL |
| | BUILDING (BLDG J-6) LOCATED AT THE FAR EAST OF THE |
| | PARKING LOT. |
| | |
| | SHEET LP-1: ENSURE TREES AND SHRUBS WILL NOT (OR IN |
| | FUTURE) OBSTRUCT ACCESS TO FIRE PROTECTION EQUIPMENT. |
| | PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS AND FIRE |
| | PROTECTION EQUIPMENT SHALL BE PROVIDED WITH CLEARANCES |
| | OF 7'-6" TO THE FRONT AND SIDES AND 4' TO THE BACKSIDE. |
| | |
| | SHEET A2.0: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE |
| | BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL |
| | BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES |
| | IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION |
| | 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES |
| | SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE |
| | DESIGN OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER |
| | FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC |
| | SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION |
| | DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA |
| | FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL." PER SECTION 12.3.4.3.3, PROVIDE |
| | SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY |
| | OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300 |
| | OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY |
| | VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. PROVIDE A |
| | PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING |
| | OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE |
| | BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE |
| | BUILDING IMMEDIATELY. |
| | |
| | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK |
| | SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH |
| | AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED |
| | EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION |
| | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE |
| | SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING |
| | MATERIALS SHALL BE PROVIDED. |
| | |