Plan Review Notes
Plan Review Notes For Permit 13070818
Permit Number 13070818
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2013-07-30 17:42:431801 PALM BEACH LAKES BOULEVARD
 PERMIT #13070818
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: THE ADDRESS OF 1721 PALM BEACH LAKES BOULEVARD
 APPEARS TO HAVE ALREADY BEEN ASSIGNED ANOTHER MALL
 BUILDING (BLDG J-6) LOCATED AT THE FAR EAST OF THE
 PARKING LOT.
  
 SHEET LP-1: ENSURE TREES AND SHRUBS WILL NOT (OR IN
 FUTURE) OBSTRUCT ACCESS TO FIRE PROTECTION EQUIPMENT.
 PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS AND FIRE
 PROTECTION EQUIPMENT SHALL BE PROVIDED WITH CLEARANCES
 OF 7'-6" TO THE FRONT AND SIDES AND 4' TO THE BACKSIDE.
  
 SHEET A2.0: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL
 BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES
 IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL." PER SECTION 12.3.4.3.3, PROVIDE
 SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300
 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. PROVIDE A
 PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING
 OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  