Plan Review Notes
Plan Review Notes For Permit 13070818
Permit Number 13070818
Review Stop E
Sequence Number 1
Notes
Date Text
2013-09-04 12:18:11 
 FIRST REVIEW 9-4-13
  
 1. ALL LV SYSTEMS WILL REQUIRE SEPARATE APPLICATIONS
 AND PERMITS
 2. ALL LV CABLES INSTALLED UNDERGROUND OR IN THE
 SLAB,WHETHER IN CONDUIT OR NOT, SHALL BE RATED AS A WET
 LOCATION AND CABLES SHALL BE LISTED FOR SUCH USE
 3. ALL OUTDOOR GFCI RECPTS SHALL HAVE IN USE TYPE
 COVERS. REVISE NOTE 21 ON PAGE E0,1
 4. ARC FLASH PROTECTION LABELING SHALL BE AFFIXED TO
 ELECTRICAL EQUIPMENT PER NEC 110.16
 5. PROVIDE SPECIFICATIONS FOR LIGHTING CONTRIL PANEL
 6. ALL LIGHTING SHALL CONFORM TO FBC ENERGY CODE
 SECTION 505, (SUCH AS DESIGNATED NIGHT LIGHTING)
 7. PROVIDE CUT SHEETS WITH MOUNTING DETAILS FOR
 CHANDELIERS AND ANY FIXTURES OVER 50 POUNDS
  
 END OF FIRST REVIEW - VB