| Plan Review Notes For Permit 13070818 |
| Permit Number |
13070818 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-04 12:18:11 | | | | FIRST REVIEW 9-4-13 | | | | | | 1. ALL LV SYSTEMS WILL REQUIRE SEPARATE APPLICATIONS | | | AND PERMITS | | | 2. ALL LV CABLES INSTALLED UNDERGROUND OR IN THE | | | SLAB,WHETHER IN CONDUIT OR NOT, SHALL BE RATED AS A WET | | | LOCATION AND CABLES SHALL BE LISTED FOR SUCH USE | | | 3. ALL OUTDOOR GFCI RECPTS SHALL HAVE IN USE TYPE | | | COVERS. REVISE NOTE 21 ON PAGE E0,1 | | | 4. ARC FLASH PROTECTION LABELING SHALL BE AFFIXED TO | | | ELECTRICAL EQUIPMENT PER NEC 110.16 | | | 5. PROVIDE SPECIFICATIONS FOR LIGHTING CONTRIL PANEL | | | 6. ALL LIGHTING SHALL CONFORM TO FBC ENERGY CODE | | | SECTION 505, (SUCH AS DESIGNATED NIGHT LIGHTING) | | | 7. PROVIDE CUT SHEETS WITH MOUNTING DETAILS FOR | | | CHANDELIERS AND ANY FIXTURES OVER 50 POUNDS | | | | | | END OF FIRST REVIEW - VB |
|