| 2013-08-05 08:51:22 | BUILDING PLAN REVIEW |
| | PERMIT: 13070818 |
| | ADD: 1801 PALM BEACH LAKES (WILL NEED TO BE CORRECTED, |
| | THIS IS THE OVERALL SITE ADDRESS) |
| | CONT: HALEY CONSTRUCTION, INC |
| | TEL: (386)566-7437 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: AUGUST 05/ 2012 |
| | ACTION: DENIED |
| | |
| | 1A) PLEASE CORRECT THE ADDRESS ON BOTH THE PERMIT |
| | APPLICATION AND PLANS. THE PERMIT APPLICATION READS |
| | 1801 PALM BEACH LAKES WHICH IS THE OVER ALL SITE |
| | ADDRESS, AND THE PLANS INDICATE A ADDRESSS OF 1721 |
| | WHICH IS ASSIGNED TO BUILDINF J-6 OF THE PLAM BEACH |
| | OUTLET MALL. SHEEET C-3 INDICATES THE LOCATION OF THE |
| | BUILDING AS A OUT PARCEL LOCATED AT THE SITE 1801 PALM |
| | BEACH LAKES. |
| | |
| | 1B) THE PERMIT APPLICATION INDICATES A VALUE OF |
| | $500,000.00. CALCULATED VALUE OF PROJECT IS |
| | $960,000.00. |
| | W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| | ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| | AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| | A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION.IF, IN THE OPINION OF |
| | THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER |
| | ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL, |
| | PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE |
| | WORK (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD |
| | AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION |
| | REFRENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF |
| | NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 1C) PROJECTS LOCATED AT THE PALM BEACH OUTLET MALL |
| | REQUIRE THE PLANS TO BE STAMPED REVIEWED BY PALM BEACH |
| | OUTLET MALL. |
| | |
| | 2) THE ARCHITECTURAL SHEETS ARE SIGNED BY RUBBER STAMP |
| | NOT AN ORIGINAL SIGNATURE. PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL |
| | HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL |
| | AFFIXED TO THE DOCUMENT. FL ADMIN CODE 61G16.003 |
| | ARCHITECTS |
| | |
| | 3) THE STRUCTURAL SHEETS ARE NOT SIGNED NOR SEALED, |
| | BEFORE PERMIT ISSUANCE THEY WILL NEED TO MEET THE |
| | REQUIREMENTS OF : |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY |
| | THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN |
| | PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | |
| | 4) SHEET S0.0 UNDER THE HEADING OF SPECIAL INSPECTION |
| | NOTES INDICATES THE OWNER TO PROVIDE A SPCEIAL |
| | INSPECTOR. PLEASE BE AWARE THE TERM SPECIAL INSPECTOR |
| | RELATES TO FL S 553.79 SPECIAL INSPECTORS FOR THRESHOLD |
| | BUILDINGS. THIS BUILDING MAY BE AN A2 ASSEMBLY BUILDING |
| | AND OVER 5,000 SQ FT BUT DOESN'T HAVE AN OCCUPANT LOAD |
| | OF 500 THEREFORE A SPECIAL INSPECTOR IS NOT REQUIRED BY |
| | FL S 553.79. |
| | |
| | THE OWNER MAY WANT TO HIRE ON A RESIDENT INSPECTOR TO |
| | OVERSEE THE STRUCTURAL JOBSITE INSPECTIONS.AMENDMENT TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 2010 EDITION, WEST PALM BEACH 110.3.9 THE BUILDING |
| | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE |
| | BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. |
| | HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED |
| | INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION |
| | HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND |
| | RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION |
| | OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH |
| | REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY |
| | A RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | |
| | SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| | WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| | BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| | ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| | CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| | INSPECTORS SHALL SUBMIT |
| | WEEKLY PROGRESS REPORTS INCLUDING THE DAILY INSPECTIONS |
| | TO THE BUILDING OFFICIAL, AND INCLUDING A CODE |
| | COMPLIANCE OPINION OF THE RESIDENT INSPECTOR. |
| | |
| | AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT, |
| | SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF |
| | COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE |
| | WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN |
| | ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION |
| | SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A |
| | CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION |
| | IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT |
| | ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS. |
| | |
| | PLEASE CONTACT KEN CONRAD THE MANAGER OF THE RESIDENT |
| | INSPECTOR PROGRAM FOR REQUIREMENTS AND DOCUMENTS THAT |
| | MUST BE SUBMITTED FOR A RESIDENT INSPECTOR TO BE |
| | APPROVED WITHIN THE CITY OF WEST PALM BEACH. CONTACT |
| | INFO; |
| | KEN CONRAD CHIEF BUILDING INSPECTOR |
| | TEL: 561-805-6666 |
| | FAX: 561-805- 6676 |
| | E-MAIL: KCONRAD @WPB.ORG |
| | |
| | 5) PLEASE SUBMIT 3 SETS OF PLANS AND PRODUCT APPROVALS |
| | (STRUCTURAL & ACHITECTURAL) FOR THE RESIDENT INSPECTOR, |
| | 1 SET FOR THE CONTRACTOR, ONE SET FOR THE RESIDENT |
| | INSPECTOR AND THE THIRD WILL BE THE OFFICE FILE SET. |
| | |
| | 6) MISSING SOILS REPORT 2010 FBC-B 1803.5.2 |
| | QUESTIONABLE SOILS. |
| | 1803.6 REPORTING. |
| | WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A |
| | WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED |
| | TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED |
| | AGENT AT THE TIME OF PERMIT APPLICATION. THIS |
| | GEOTECHNICAL REPORT SHALL INCLUDE, BUT NEED NOT BE |
| | LIMITED TO, THE FOLLOWING INFORMATION: |
| | 6.1. A PLOT SHOWING THE LOCATION OF THE SOIL |
| | INVESTIGATIONS. |
| | 6.2. A COMPLETE RECORD OF THE SOIL BORING AND |
| | PENETRATION TEST LOGS AND SOIL SAMPLES. |
| | 6.3. A RECORD OF THE SOIL PROFILE. |
| | 6.4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED. |
| | 6.5. RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN |
| | CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING |
| | CAPACITY OF NATURAL OR COMPACTED SOIL; PROVISIONS TO |
| | MITIGATE THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF |
| | THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT |
| | AND VARYING SOIL STRENGTH; AND THE EFFECTS OF ADJACENT |
| | LOADS. |
| | 6.6. EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT. |
| | |
| | 7) SHEET G1.0; |
| | 7A) OCCUPANT LOAD CALCULATIONS ARE ALL GIVEN UNDER THE |
| | FFPC, PLEASE PROVIDE THE SAME CALCULATIONS UNDER THE |
| | 2010 FBC-B TABLE 1004.1.1. THE BAR IS CHAIRS ONLY, |
| | CONCENTRATED 7 SQ FT/ OCCUPANT. THE SECOND QUESTION IS |
| | THE OCCUPANT LOAD STATED A NET FIGURE THAT ALLOWS FOR |
| | THE AREA USED FOR PERMANENT BUILDING COMPONENTS, SUCH |
| | AS SHAFTS, FIXED EQUIPMENT, THICKNESS OF WALLS, |
| | CORRIDORS, TOILET ROOMS, MECHANICAL ROOMS AND CLOSETS |
| | ARE NOT TO BE INCLUDED IN THE NET FLOOR AREA. |
| | |
| | 7B) CODE INFORMATION, BUILDING DESCRIPTION INDICATES |
| | THIS BUILDING TO BE A VB- SPRINKLERED BUILDING. AREA |
| | INCREASES WERE TAKEN FOR A FIRE SPRINKLERED BUILDING |
| | BUT NO FIRE SPRINKLER PLANS WERE SUBMITTED. |
| | |
| | 8) SHEET G1.0 NOR THE C-3 PROVIDE A ANALYSIS ON |
| | ACCESSIBLE PARKING AND HOW COMPLIANCE WITH 2010 FL |
| | ACCESSIBILITY CODE TABLE 208.2 WAS ACHIEVED? |
| | |
| | 9) SHEET C6 SHOWS PARKING STALL LINES AS SINGLE |
| | STRIPED, PLEASE SEE WEST PALM BEACH ZONING CODE FOR |
| | DOUBLE STRIPPING. |
| | |
| | |
| | 10) SHEET A0.1 & A0.1A IS ANSI 117.1, PLEASE REFER TO |
| | THE 2010 FBC-ACCESSIBILITY CODE. FLORIDA STATUTE 553.80 |
| | PROVIDES FOR THE ENFORCEMENT |
| | OF THIS PART OF THE CODE, THE DEPARTMEENT OF JUSTICE |
| | HAS CERTIFIED THIS CODE. |
| | |
| | 11) SHEET A1.0; |
| | |
| | 11A) SHEET A1.0, A1. A1.2 & A4.2 DETAIL # 15 ALL |
| | INDICATE A STAIR TREAD OF 11". PLEASE SHOW COMPLIANCE |
| | WITH 2010 FBC-B 1003.5 EXCEPTION # 2 THAT REQUIRES A 13 |
| | INCH TREAD, ALSO REVIEW HANDRAIL REQUIREMENTS. |
| | |
| | 11B) SHEET A1.0, A1.2 & A4.2 DETAIL # 18 INDICATE A ONE |
| | FOOT DIFFERENCE IN GRADE, THESE DETAILS DO NOT SHOW |
| | COMPLIANCE WITH FBC-B 1003.5 ELEVATION CHANGE. |
| | |
| | 12) SHEET A1.1 THE EMPLOYEES RESTROOM # 117 , THE |
| | INSWING DOOR SWINGS OVER THE CLEAR FLOOR SPACE REQUIRED |
| | FOR THE WATER CLOSET. 2010 FL ACCESSIBILITY CODE |
| | 604.3.2 NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE |
| | LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | PLEASE NOTE: 603.2.3 DOOR SWING. |
| | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| | EXCEPTIONS: 2. WHERE THE TOILET ROOM OR BATHING ROOM IS |
| | FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING |
| | WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC |
| | OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING |
| | INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR |
| | ANY FIXTURE. |
| | |
| | 13A) SHEET A1.1 , A3.4-01 & S1.0 DEAL WITH AN ATTIC |
| | ACCESS, AND ATTIC, AND ACCESS TO THE ROOF TOP. THE |
| | PLANS ARE NOT CLEAR HOW YOU LEAVE THE LOWER LADDER AND |
| | TRANSVERSE ACROSS THE FLOOR DECK TO GAIN ACCESS TO THE |
| | UPPER LADDER TO GAIN ACCESS TO THE ROOF LEVEL. THERE IS |
| | TWO ISSUES AT HAND, VERTICAL ACCESS TO THE ROOF AS WELL |
| | AS ATTIC STORAGE WITHOUT SEPERATION. 10107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 13B) THE PLANS ALSO FAIL TO PROVIDE WHERE THE WALLS ARE |
| | LOCATED AROUND THE VERTICAL ACCESS SCUTTLE HOLE AS WELL |
| | AS THE STORAGE AERA? 107.2.1.3. ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 13C) SHOW COMPLIANCE WITH: 413.2 ATTIC, UNDER-FLOOR AND |
| | CONCEALED SPACES. |
| | ATTIC, UNDER-FLOOR AND CONCEALED SPACES USED FOR |
| | STORAGE OF COMBUSTIBLE MATERIALS SHALL BE PROTECTED ON |
| | THE STORAGE SIDE AS REQUIRED FOR 1-HOUR |
| | FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE |
| | PROTECTED BY ASSEMBLIES THAT ARE SELF-CLOSING AND ARE |
| | OF NONCOMBUSTIBLE CONSTRUCTION OR SOLID WOOD CORE NOT |
| | LESS THAN 13/4 INCH (45 MM) IN THICKNESS. |
| | EXCEPTIONS: 1. AREAS PROTECTED BY APPROVED AUTOMATIC |
| | SPRINKLER SYSTEMS. |
| | |
| | 13D) 703.6 MARKING AND IDENTIFICATION. FIRE WALLS, FIRE |
| | BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE |
| | PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED |
| | OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING. SUCH |
| | IDENTIFICATION SHALL: 1. BE LOCATED IN ACCESSIBLE |
| | CONCEALED FLOOR, FLOOR-CEILING OR ATTIC SPACES; |
| | |
| | 13E) DRAFTSTOPPING IN ATTICS: 17.4.3 OTHER GROUPS. |
| | DRAFTSTOPPING SHALL BE INSTALLED IN ATTICS AND |
| | CONCEALED ROOF SPACES, SUCH THAT ANY HORIZONTAL AREA |
| | DOES NOT EXCEED 3,000 SQUARE FEET (279 M2). EXCEPTION: |
| | DRAFTSTOPPING IS NOT REQUIRED IN BUILDINGS EQUIPPED |
| | THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH SECTION 903.3.1.1 |
| | |
| | 13F) PLEASE PROVIDE THE FLOOR LOADING OF THE ATTIC |
| | SPACE STORAGE, ABOVE GRADE LEVEL TO COMPLY WITH 2010 |
| | FBC-B TABLE 1607.1 (36) 125 PSF LIGHT. |
| | |
| | 13G) THE STRUCTURAL SHEET S1 KEY NOTE # 1 INDICATES THE |
| | NORTH SOUTH BEARING WALL CONTINUES TO GRID LINE # 3 |
| | DOES THE ENCLOSED AND RAISED STORAGE CLOSET CONTINUE |
| | NORTH TO GRID LINE # 3? |
| | |
| | 14A) SHEET A5.0 INDICATES IN THE DOOR SCHEDULE DOOR # |
| | 15 & 15A PATIO DINING, GATE # 15 IT APPEARS TO BE |
| | BLOCKED BY TABLES AND 15A NOT SHOWN ON PLANS BUT THERE |
| | IS A UNMARKED GATE LOCATION? DISCREPANCY IN PLANS |
| | 107.2.1.3. |
| | |
| | 14B) THE DOOR SCHEDULE FOR DOOR 15, 15A INDICATES |
| | HARDWARE GROUP # 6 PLANS DO NOT INCLUDE PANIC HARDWARE. |
| | 1008.2 GATES. GATES SERVING THE MEANS OF EGRESS SYSTEM |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THIS SECTION. |
| | GATES USED AS A COMPONENT IN A MEANS OF EGRESS SHALL |
| | CONFORM TO THE APPLICABLE REQUIREMENTS FOR DOORS. |
| | 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING |
| | ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN |
| | A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A |
| | LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE. |
| | |
| | 15) SHEET S4.0: |
| | 15A) WIND PRESSURES, PLEASE PROVIDE AT WHAT THE MEAN |
| | ROOF HEIGHT THSES VALUES ARE FOR ? ASSUMED 20'-0". |
| | |
| | 15B) PLEASE PROVIDE IF THESE PRESSURES ARE IN V-ULT OR |
| | VASD? ASSUMED VULT. |
| | |
| | 15C) PLEASE PROVIDE THE PRESURES IN VASD SINCE THE |
| | PRODUCT APPROVALS ARE ALL IN VASD, IT APPEARS THE ROOF |
| | PRESSURES ARE CORRECT BUT THE |
| | WALL ZONES 4 & 5 APPEAR TO BE LOW IN PRESSURE ZONE 4 & |
| | ZONE 5. 132 MPH VASD 20' MEAN ROOF HEIGHT, EXP "C" |
| | ZONE 4/ 10 SQ FT +40.4/ -43.8 |
| | ZONE 5/ 10 SQ FT +40.4/ 54.1 |
| | |
| | 16) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 17) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 18) SHEET S4.1 A/C STANDS ARE TO COMPLY WITH 2010 FBC-B |
| | 1509.7 MECHANICAL UNITS. |
| | ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS |
| | RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF |
| | SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE |
| | UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM |
| | CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7. |
| | |
| | 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |