Plan Review Notes
Plan Review Notes For Permit 13070818
Permit Number 13070818
Review Stop B
Sequence Number 1
Notes
Date Text
2013-08-05 08:51:22BUILDING PLAN REVIEW
 PERMIT: 13070818
 ADD: 1801 PALM BEACH LAKES (WILL NEED TO BE CORRECTED,
 THIS IS THE OVERALL SITE ADDRESS)
 CONT: HALEY CONSTRUCTION, INC
 TEL: (386)566-7437
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 05/ 2012
 ACTION: DENIED
  
 1A) PLEASE CORRECT THE ADDRESS ON BOTH THE PERMIT
 APPLICATION AND PLANS. THE PERMIT APPLICATION READS
 1801 PALM BEACH LAKES WHICH IS THE OVER ALL SITE
 ADDRESS, AND THE PLANS INDICATE A ADDRESSS OF 1721
 WHICH IS ASSIGNED TO BUILDINF J-6 OF THE PLAM BEACH
 OUTLET MALL. SHEEET C-3 INDICATES THE LOCATION OF THE
 BUILDING AS A OUT PARCEL LOCATED AT THE SITE 1801 PALM
 BEACH LAKES.
  
 1B) THE PERMIT APPLICATION INDICATES A VALUE OF
 $500,000.00. CALCULATED VALUE OF PROJECT IS
 $960,000.00.
 W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES.
 ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT,
 A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN
 ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE
 APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFRENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 1C) PROJECTS LOCATED AT THE PALM BEACH OUTLET MALL
 REQUIRE THE PLANS TO BE STAMPED REVIEWED BY PALM BEACH
 OUTLET MALL.
  
 2) THE ARCHITECTURAL SHEETS ARE SIGNED BY RUBBER STAMP
 NOT AN ORIGINAL SIGNATURE. PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL
 HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL
 AFFIXED TO THE DOCUMENT. FL ADMIN CODE 61G16.003
 ARCHITECTS
  
 3) THE STRUCTURAL SHEETS ARE NOT SIGNED NOR SEALED,
 BEFORE PERMIT ISSUANCE THEY WILL NEED TO MEET THE
 REQUIREMENTS OF :
 FL ADMIN CODE 61G15-23.002 ENGINEERS PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 4) SHEET S0.0 UNDER THE HEADING OF SPECIAL INSPECTION
 NOTES INDICATES THE OWNER TO PROVIDE A SPCEIAL
 INSPECTOR. PLEASE BE AWARE THE TERM SPECIAL INSPECTOR
 RELATES TO FL S 553.79 SPECIAL INSPECTORS FOR THRESHOLD
 BUILDINGS. THIS BUILDING MAY BE AN A2 ASSEMBLY BUILDING
 AND OVER 5,000 SQ FT BUT DOESN'T HAVE AN OCCUPANT LOAD
 OF 500 THEREFORE A SPECIAL INSPECTOR IS NOT REQUIRED BY
 FL S 553.79.
  
 THE OWNER MAY WANT TO HIRE ON A RESIDENT INSPECTOR TO
 OVERSEE THE STRUCTURAL JOBSITE INSPECTIONS.AMENDMENT TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 2010 EDITION, WEST PALM BEACH 110.3.9 THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE
 BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109.
 HE/SHE MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED
 INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION
 HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND
 RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION
 OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH
 REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY
 A RESPONSIBLE OFFICER OF SUCH SERVICE.
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT
 WEEKLY PROGRESS REPORTS INCLUDING THE DAILY INSPECTIONS
 TO THE BUILDING OFFICIAL, AND INCLUDING A CODE
 COMPLIANCE OPINION OF THE RESIDENT INSPECTOR.
  
 AT THE COMPLETION OF THE CONSTRUCTION WORK OR PROJECT,
 SUCH INSPECTORS SHALL SUBMIT A CERTIFICATE OF
 COMPLIANCE TO THE BUILDING OFFICIAL, STATING THAT THE
 WORK WAS DONE IN COMPLIANCE WITH THIS CODE AND IN
 ACCORDANCE WITH THE PERMITTED DRAWING. FINAL INSPECTION
 SHALL BE MADE BY THE BUILDING OFFICIAL BEFORE A
 CERTIFICATE OF OCCUPANCY OR CERTIFICATE OF COMPLETION
 IS ISSUED; AND CONFIRMATION INSPECTIONS MAY BE MADE AT
 ANY TIME TO MONITOR ACTIVITIES AND RESIDENT INSPECTORS.
  
 PLEASE CONTACT KEN CONRAD THE MANAGER OF THE RESIDENT
 INSPECTOR PROGRAM FOR REQUIREMENTS AND DOCUMENTS THAT
 MUST BE SUBMITTED FOR A RESIDENT INSPECTOR TO BE
 APPROVED WITHIN THE CITY OF WEST PALM BEACH. CONTACT
 INFO;
 KEN CONRAD CHIEF BUILDING INSPECTOR
 TEL: 561-805-6666
 FAX: 561-805- 6676
 E-MAIL: KCONRAD @WPB.ORG
  
 5) PLEASE SUBMIT 3 SETS OF PLANS AND PRODUCT APPROVALS
 (STRUCTURAL & ACHITECTURAL) FOR THE RESIDENT INSPECTOR,
 1 SET FOR THE CONTRACTOR, ONE SET FOR THE RESIDENT
 INSPECTOR AND THE THIRD WILL BE THE OFFICE FILE SET.
  
 6) MISSING SOILS REPORT 2010 FBC-B 1803.5.2
 QUESTIONABLE SOILS.
 1803.6 REPORTING.
 WHERE GEOTECHNICAL INVESTIGATIONS ARE REQUIRED, A
 WRITTEN REPORT OF THE INVESTIGATIONS SHALL BE SUBMITTED
 TO THE BUILDING OFFICIAL BY THE OWNER OR AUTHORIZED
 AGENT AT THE TIME OF PERMIT APPLICATION. THIS
 GEOTECHNICAL REPORT SHALL INCLUDE, BUT NEED NOT BE
 LIMITED TO, THE FOLLOWING INFORMATION:
 6.1. A PLOT SHOWING THE LOCATION OF THE SOIL
 INVESTIGATIONS.
 6.2. A COMPLETE RECORD OF THE SOIL BORING AND
 PENETRATION TEST LOGS AND SOIL SAMPLES.
 6.3. A RECORD OF THE SOIL PROFILE.
 6.4. ELEVATION OF THE WATER TABLE, IF ENCOUNTERED.
 6.5. RECOMMENDATIONS FOR FOUNDATION TYPE AND DESIGN
 CRITERIA, INCLUDING BUT NOT LIMITED TO: BEARING
 CAPACITY OF NATURAL OR COMPACTED SOIL; PROVISIONS TO
 MITIGATE THE EFFECTS OF EXPANSIVE SOILS; MITIGATION OF
 THE EFFECTS OF LIQUEFACTION, DIFFERENTIAL SETTLEMENT
 AND VARYING SOIL STRENGTH; AND THE EFFECTS OF ADJACENT
 LOADS.
 6.6. EXPECTED TOTAL AND DIFFERENTIAL SETTLEMENT.
  
 7) SHEET G1.0;
 7A) OCCUPANT LOAD CALCULATIONS ARE ALL GIVEN UNDER THE
 FFPC, PLEASE PROVIDE THE SAME CALCULATIONS UNDER THE
 2010 FBC-B TABLE 1004.1.1. THE BAR IS CHAIRS ONLY,
 CONCENTRATED 7 SQ FT/ OCCUPANT. THE SECOND QUESTION IS
 THE OCCUPANT LOAD STATED A NET FIGURE THAT ALLOWS FOR
 THE AREA USED FOR PERMANENT BUILDING COMPONENTS, SUCH
 AS SHAFTS, FIXED EQUIPMENT, THICKNESS OF WALLS,
 CORRIDORS, TOILET ROOMS, MECHANICAL ROOMS AND CLOSETS
 ARE NOT TO BE INCLUDED IN THE NET FLOOR AREA.
  
 7B) CODE INFORMATION, BUILDING DESCRIPTION INDICATES
 THIS BUILDING TO BE A VB- SPRINKLERED BUILDING. AREA
 INCREASES WERE TAKEN FOR A FIRE SPRINKLERED BUILDING
 BUT NO FIRE SPRINKLER PLANS WERE SUBMITTED.
  
 8) SHEET G1.0 NOR THE C-3 PROVIDE A ANALYSIS ON
 ACCESSIBLE PARKING AND HOW COMPLIANCE WITH 2010 FL
 ACCESSIBILITY CODE TABLE 208.2 WAS ACHIEVED?
  
 9) SHEET C6 SHOWS PARKING STALL LINES AS SINGLE
 STRIPED, PLEASE SEE WEST PALM BEACH ZONING CODE FOR
 DOUBLE STRIPPING.
  
  
 10) SHEET A0.1 & A0.1A IS ANSI 117.1, PLEASE REFER TO
 THE 2010 FBC-ACCESSIBILITY CODE. FLORIDA STATUTE 553.80
 PROVIDES FOR THE ENFORCEMENT
 OF THIS PART OF THE CODE, THE DEPARTMEENT OF JUSTICE
 HAS CERTIFIED THIS CODE.
  
 11) SHEET A1.0;
  
 11A) SHEET A1.0, A1. A1.2 & A4.2 DETAIL # 15 ALL
 INDICATE A STAIR TREAD OF 11". PLEASE SHOW COMPLIANCE
 WITH 2010 FBC-B 1003.5 EXCEPTION # 2 THAT REQUIRES A 13
 INCH TREAD, ALSO REVIEW HANDRAIL REQUIREMENTS.
  
 11B) SHEET A1.0, A1.2 & A4.2 DETAIL # 18 INDICATE A ONE
 FOOT DIFFERENCE IN GRADE, THESE DETAILS DO NOT SHOW
 COMPLIANCE WITH FBC-B 1003.5 ELEVATION CHANGE.
  
 12) SHEET A1.1 THE EMPLOYEES RESTROOM # 117 , THE
 INSWING DOOR SWINGS OVER THE CLEAR FLOOR SPACE REQUIRED
 FOR THE WATER CLOSET. 2010 FL ACCESSIBILITY CODE
 604.3.2 NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE
 LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
 PLEASE NOTE: 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTIONS: 2. WHERE THE TOILET ROOM OR BATHING ROOM IS
 FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING
 WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC
 OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO SWING
 INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR
 ANY FIXTURE.
  
 13A) SHEET A1.1 , A3.4-01 & S1.0 DEAL WITH AN ATTIC
 ACCESS, AND ATTIC, AND ACCESS TO THE ROOF TOP. THE
 PLANS ARE NOT CLEAR HOW YOU LEAVE THE LOWER LADDER AND
 TRANSVERSE ACROSS THE FLOOR DECK TO GAIN ACCESS TO THE
 UPPER LADDER TO GAIN ACCESS TO THE ROOF LEVEL. THERE IS
 TWO ISSUES AT HAND, VERTICAL ACCESS TO THE ROOF AS WELL
 AS ATTIC STORAGE WITHOUT SEPERATION. 10107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 13B) THE PLANS ALSO FAIL TO PROVIDE WHERE THE WALLS ARE
 LOCATED AROUND THE VERTICAL ACCESS SCUTTLE HOLE AS WELL
 AS THE STORAGE AERA? 107.2.1.3. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 13C) SHOW COMPLIANCE WITH: 413.2 ATTIC, UNDER-FLOOR AND
 CONCEALED SPACES.
 ATTIC, UNDER-FLOOR AND CONCEALED SPACES USED FOR
 STORAGE OF COMBUSTIBLE MATERIALS SHALL BE PROTECTED ON
 THE STORAGE SIDE AS REQUIRED FOR 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION. OPENINGS SHALL BE
 PROTECTED BY ASSEMBLIES THAT ARE SELF-CLOSING AND ARE
 OF NONCOMBUSTIBLE CONSTRUCTION OR SOLID WOOD CORE NOT
 LESS THAN 13/4 INCH (45 MM) IN THICKNESS.
 EXCEPTIONS: 1. AREAS PROTECTED BY APPROVED AUTOMATIC
 SPRINKLER SYSTEMS.
  
 13D) 703.6 MARKING AND IDENTIFICATION. FIRE WALLS, FIRE
 BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE
 PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED
 OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING. SUCH
 IDENTIFICATION SHALL: 1. BE LOCATED IN ACCESSIBLE
 CONCEALED FLOOR, FLOOR-CEILING OR ATTIC SPACES;
  
 13E) DRAFTSTOPPING IN ATTICS: 17.4.3 OTHER GROUPS.
 DRAFTSTOPPING SHALL BE INSTALLED IN ATTICS AND
 CONCEALED ROOF SPACES, SUCH THAT ANY HORIZONTAL AREA
 DOES NOT EXCEED 3,000 SQUARE FEET (279 M2). EXCEPTION:
 DRAFTSTOPPING IS NOT REQUIRED IN BUILDINGS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1
  
 13F) PLEASE PROVIDE THE FLOOR LOADING OF THE ATTIC
 SPACE STORAGE, ABOVE GRADE LEVEL TO COMPLY WITH 2010
 FBC-B TABLE 1607.1 (36) 125 PSF LIGHT.
  
 13G) THE STRUCTURAL SHEET S1 KEY NOTE # 1 INDICATES THE
 NORTH SOUTH BEARING WALL CONTINUES TO GRID LINE # 3
 DOES THE ENCLOSED AND RAISED STORAGE CLOSET CONTINUE
 NORTH TO GRID LINE # 3?
  
 14A) SHEET A5.0 INDICATES IN THE DOOR SCHEDULE DOOR #
 15 & 15A PATIO DINING, GATE # 15 IT APPEARS TO BE
 BLOCKED BY TABLES AND 15A NOT SHOWN ON PLANS BUT THERE
 IS A UNMARKED GATE LOCATION? DISCREPANCY IN PLANS
 107.2.1.3.
  
 14B) THE DOOR SCHEDULE FOR DOOR 15, 15A INDICATES
 HARDWARE GROUP # 6 PLANS DO NOT INCLUDE PANIC HARDWARE.
 1008.2 GATES. GATES SERVING THE MEANS OF EGRESS SYSTEM
 SHALL COMPLY WITH THE REQUIREMENTS OF THIS SECTION.
 GATES USED AS A COMPONENT IN A MEANS OF EGRESS SHALL
 CONFORM TO THE APPLICABLE REQUIREMENTS FOR DOORS.
 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 15) SHEET S4.0:
 15A) WIND PRESSURES, PLEASE PROVIDE AT WHAT THE MEAN
 ROOF HEIGHT THSES VALUES ARE FOR ? ASSUMED 20'-0".
  
 15B) PLEASE PROVIDE IF THESE PRESSURES ARE IN V-ULT OR
 VASD? ASSUMED VULT.
  
 15C) PLEASE PROVIDE THE PRESURES IN VASD SINCE THE
 PRODUCT APPROVALS ARE ALL IN VASD, IT APPEARS THE ROOF
 PRESSURES ARE CORRECT BUT THE
 WALL ZONES 4 & 5 APPEAR TO BE LOW IN PRESSURE ZONE 4 &
 ZONE 5. 132 MPH VASD 20' MEAN ROOF HEIGHT, EXP "C"
 ZONE 4/ 10 SQ FT +40.4/ -43.8
 ZONE 5/ 10 SQ FT +40.4/ 54.1
  
 16) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 17) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 18) SHEET S4.1 A/C STANDS ARE TO COMPLY WITH 2010 FBC-B
 1509.7 MECHANICAL UNITS.
 ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS
 RAISED A MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF
 SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE
 UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM
 CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
  
 19) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  