| Plan Review Notes For Permit 13070787 |
| Permit Number |
13070787 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-09-18 20:19:53 | ****PROVISO**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | ****REVISION REQUIRED BEFORE FIRST INSPECTION**** | | | | | | | | | 1. SEE PREVIOUS LIST REGARDING DISCREPANCIES IN | | | BUILDING TYPE ON SHEET 1 OF PLAN. THE PLANS WERE | | | REVISED TO STATE A VA BUILDING TYPE AND ALSO TYPE IIIA, | | | BOTH WHICH REQUIRE A FIRE RATING FOR STRUCTURAL | | | ELEMENTS. EITHER REVISE BUILDING TYPE OR PROVIDE | | | DETAILS AS TO HOW THE FIRE RATED STRUCTURAL ELEMENTS | | | ARE OR WILL BE PROTECTED FBC TABLE 601. **REVISE SHEET | | | 1** | | | | | | 2. SEE PREVIOUS LISTS REGARDING PRODUCT APPROVALS | | | REQUIRED TO BE REVIEWED BY DESIGNER OF RECORD. SUBMIT | | | PRODUCT APPROVALS ***AS A REVISION*** FOR ALL | | | COMPONENTS & CLADDING, ***REVIEWED BY DESIGNER OF | | | RECORD*** (SHOP DRAWING REVIEW STAMP OR LETTER) PRIOR | | | TO INSTALLATION. ALL WERE SUBMITTED BUT NONE WERE | | | REVIEWED BY DESIGNER OF RECORD AS REQUIRED. | | | PRODUCT APPROVALS REQUIRED: ROOF, DOORS, SINGLE HUNG | | | WINDOWS, STOREFRONT, MECHANICAL STAND | | | | | | 3. ROOF INFORMATION REQUESTED NOT PROVIDED. SEE ITEM 2, | | | REVIEW BY DOR REQUIRED. SUBMIT ENGINEERING FOR ROOFING | | | PERMIT 13090352 AS A REVISION | | | | | | | | | | | | |
|