| 2013-08-31 14:10:05 | ****CORRECTIONS**** |
| | |
| | WHEN RESUBMITTING, PLEASE PROVIDE NEW SHEETS 5 AND 6 IN |
| | ADDITION TO SHEETS WHICH HAVE CHANGED AS WELL AS |
| | PRODUCT APPROVALS SUBMITTED FIRST REVIEW |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. SEE PREVIOUS LIST REGARDING DISCREPANCIES IN |
| | BUILDING TYPE ON SHEET 1 OF PLAN. THE PLANS WERE |
| | REVISED TO STATE A VA BUILDING TYPE AND ALSO TYPE IIIA, |
| | BOTH WHICH REQUIRE A FIRE RATING FOR STRUCTURAL |
| | ELEMENTS. EITHER REVISE BUILDING TYPE OR PROVIDE |
| | DETAILS AS TO HOW THE FIRE RATED STRUCTURAL ELEMENTS |
| | ARE OR WILL BE PROTECTED FBC TABLE 601. |
| | |
| | 2. SEE PREVIOUS LIST REGARDING PRODUCT APPROVALS |
| | REQUIRED TO BE REVIEWED BY DESIGNER OF RECORD. SUBMIT |
| | PRODUCT APPROVALS ***AS A REVISION*** FOR ALL |
| | COMPONENTS & CLADDING, ***REVIEWED BY DESIGNER OF |
| | RECORD*** (SHOP DRAWING REVIEW STAMP OR LETTER) PRIOR |
| | TO INSTALLATION. |
| | |
| | 3. ROOF INFORMATION REQUESTED NOT PROVIDED. SEE ITEM 2, |
| | REVIEW BY DOR REQUIRED. SEE PREVIOUS LIST REGARDING |
| | INFORMATION REQUIRED FOR ROOF PERMITS (INDICATE |
| | ASSEMBLY PROPOSED AND PROVIDE RAS117 CALCULATIONS IF |
| | REQUIRED, PREPARED BY A DESIGN PROFESSIONAL, IF |
| | REQUIRED). SUBMIT AS A REVISION. |
| | |
| | 4. SEPARATE PLANS AND PERMIT REQUIRED FOR MECHANICAL. |
| | NO MECHANICAL PLANS SUBMITTED. |
| | |
| | 5. SEPARATE ROOF PERMIT REQUIRED. THE ROOF SUB PERMIT |
| | CANNOT BE ISSUED UNTIL THE ROOFING INFORMATION IS |
| | SUBMITTED/REVIEWED (REVISION). |
| | |
| | 6. WHEN RESUBMITTING, PLEASE PROVIDE SHEETS 5 AND 6 IN |
| | ADDITION TO ANY OTHER SHEETS WHICH HAVE CHANGED AS WELL |
| | AS PRODUCT APPROVALS SUBMITTED FIRST REVIEW (UNABLE TO |
| | LOCATE AT THIS TIME). |
| | |
| | |
| | |
| | |