Plan Review Notes
Plan Review Notes For Permit 13070787
Permit Number 13070787
Review Stop P
Sequence Number 1
Notes
Date Text
2013-07-25 13:44:46FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. PLEASE SEE BUILDING REVIEW NOTES FOR 7'-1" MINIMUM
 REQUIRED WIDTH IN THE TOILET ROOM.
 FBC ACCESSIBILITY
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 2. WHILE DRINKING FOUNTAINS ARE NOT REQUIRED FOR 15 OR
 LESS OCCUPANTS, FBC PLUMBING TABLE 403.1(E, F), IF
 DRINKING FOUNTAINS ARE PROVIDED THE ACCESSIBILITY CODE
 REQUIRES TWO (HI/ LOW).
 FBC ACCESSIBILITY 2010 211.1 GENERAL.
 WHERE DRINKING FOUNTAINS ARE PROVIDED ON AN EXTERIOR
 SITE, ON A FLOOR, OR WITHIN A SECURED AREA THEY SHALL
 BE PROVIDED IN ACCORDANCE WITH 211.
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  