| 2013-07-25 13:44:46 | FBC 2010 EXISTING BUILDING CODE |
| | FBC 2010 ACCESSIBILITY CODE |
| | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. PLEASE SEE BUILDING REVIEW NOTES FOR 7'-1" MINIMUM |
| | REQUIRED WIDTH IN THE TOILET ROOM. |
| | FBC ACCESSIBILITY |
| | 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | 604.3.2 OVERLAP. |
| | THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE |
| | PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB |
| | BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT |
| | HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE |
| | AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE |
| | TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 2. WHILE DRINKING FOUNTAINS ARE NOT REQUIRED FOR 15 OR |
| | LESS OCCUPANTS, FBC PLUMBING TABLE 403.1(E, F), IF |
| | DRINKING FOUNTAINS ARE PROVIDED THE ACCESSIBILITY CODE |
| | REQUIRES TWO (HI/ LOW). |
| | FBC ACCESSIBILITY 2010 211.1 GENERAL. |
| | WHERE DRINKING FOUNTAINS ARE PROVIDED ON AN EXTERIOR |
| | SITE, ON A FLOOR, OR WITHIN A SECURED AREA THEY SHALL |
| | BE PROVIDED IN ACCORDANCE WITH 211. |
| | 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |