Plan Review Notes
Plan Review Notes For Permit 13070787
Permit Number 13070787
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-29 15:33:239/12/13 DH
 PROVIDED PLANS BY S HILL FOR REVIEW
 NOTES PLACED ON PLANS AND SIGNED
  
  
  
 8-29-13
 ADD SERVICE RISER DIAGRAM PER NEC 215.5
 ADD PANEL SCHEDULE PER NEC 408.4
 ARE THERE ANY ELECTRICAL FIXTURES OR DEVICES? PLEASE
 SHOW THEM WITH CIRCUIRTY ON DRAWINGS
 ADD A DEMO NOTE TO REMOVE ALL ABANDONED ELECTRIC BACK
 TO ITS SOURCE. (NOTHING LEFT IN CEILING)