2013-07-26 08:17:38PLANS DENIED
 1) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROL'S.
 SHOW THE LOCATION AND THE SIZE OF THE FRESH AIR DUCT
 ON THE PLANS 2010 FLORIDA ENERGY CODE.
 2) DOORS ON AIR HANDLER CLOSET SHOW WOOD ON THE
 DOOR SCHEDULE. REFER TO SECTION 602.2.1 MATERIALS
 WITHIN
 PLENUM'S 2010 FBC (M)