| Plan Review Notes For Permit 13070764 |
| Permit Number |
13070764 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-30 16:19:17 | BASED ON ADDITIONAL RECEIVED FROM CONTRACTOR REGARDING | | | THE RATED CEILING EXISTING ABOVE THE NEW DROP CEILING, | | | PLAN IS BEING APPROVED WITH NOTES REGARDING PROTECTION | | | OF ANY PENETRATION OF RATED CEILING. PLACED BACK IN | | | DENIED UNDER "C" DUE TO MECHANICAL NOT SIGNING OFF. DH | | | 7/30/13 | | 2013-07-26 10:05:12 | PUT IN DENIED UNDER "C" DH | | | | | | PROVIDE DETAILS OF RATED PENETRATIONS, INCLUDING | | | CEILING BOXES AND OTHER ITEMS, 300.22. PROVIDE DETAILS | | | OF CEILING FIXTURE SUPPORT AND ATTACHMENT SHOWING FIRE | | | RATING DESIGN NUMBER. 410.36 |
|