| 2013-07-30 15:00:54 | DENIED UNDER "W" | | | SEE FIRE COMMENTS. | | | DOES SYSTEM ALLOW ANY ADDITIONS FOR TENNANT BUILDOUTS | | | SO REPLACEMENT OF THE MAJOR COMPONENTS WILL NOT BE | | | NEEDED? NO "FUTURE" CALCULATIONS ARE SHOWN FOR VOLTAGE | | | DROP OR BATTERY CAPACITY. |
|