| Plan Review Notes For Permit 13070754 |
| Permit Number |
13070754 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-10-23 19:36:19 | THE ELECTRICAL PLAN REVIEW SHOWED NONCOMPLIANCE WITH | | | THE REQUIREMENTS OF NEC 210.52 (A)(1) THROUGH (A)(3). | | | FILE COPY OF THE PLANS HAVE BEEN MARKED ACCORDINGLY. | | | THERE SHALL BE A FLOOR OUTLET ON THE FLOOR LINE ALONG | | | THE RAIL AS WELL AS ON THE AREAS OF THE POT SHELVING, | | | AND ANY OTHER AREA FOUND TO BE MISSING SUCH BY THE | | | FIELD INSPECTOR. | | | AS PER NEC 210. 12(B) ACFI IS REQUIRED THROUGH OUT. | | | AS PER NEC 406.11 TAMPER-RESISTANT RECEPTACLE ARE | | | REQUIRED | | | AS PER FBC 314 & 315 SMOKE DETECTORS SHALL BE REQUIRED |
|