| Plan Review Notes For Permit 13070754 |
| Permit Number |
13070754 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-30 14:51:36 | 480 HIBISCUS STREET | | | PERMIT #13070754 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | TO MINIMIZE NUISANCE ALARMS FOR THE BUILDING, THE SMOKE | | | ALARMS AND/OR CARBON MONOXIDE DETECTORS WITHIN THE | | | INDIVIDUAL RESIDENTIAL SPACES SHALL NOT BE TIED INTO | | | THE BUILDINGS FIRE ALARM SYSTEM PER SECTION 9.6.2.10.4 | | | OF NFPA 101. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | PER NFPA 72 SECTION 7.4.41, SLEEPING AREA NOTIFICATION | | | APPLICANCES SHALL HAVE A SOUND LEVEL OF AT LEAST 15 DB | | | ABOVE THE AVERAGE AMBIENT SOUND LEVEL OR 5 DB ABOVE THE | | | MAXIMUM SOUND LEVEL HAVING A DURATION OF AT LEAST 60 | | | SECONDS OR A SOUND LEVEL OF AT LEAST 75 DBA, WHICHEVER | | | IS GREATER, MEASURED AT THE PILLOW LEVEL IN THE AREA | | | REQUIRED TO BE SERVED BY THE SYSTEM USING THE | | | A-WEIGHTED SCALE (DBA). | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 |
|