| 2013-07-30 10:21:09 | BUILDING PLAN REVIEW |
| | PERMIT: 13070748 UNIT # 1 2,564 SQ FT |
| | 13070750 UNIT # 2 2,112 SQ FT |
| | 13070752 UNIT # 11 1,868 SQ FT |
| | 13070753 UNIT # 12 1,339 SQ FT |
| | 13070754 UNIT # 14 1,434 SQ FT |
| | ADD: 480 HIBISCUS ST |
| | CONT: BLUEWATER BUILDERS GROUP, INC |
| | TEL: (954)753-7233 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: JULY 30/2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A.001 UNDER THE HEADING EXISTING BUILDING |
| | CONSTRUCTION DATA, PLANS INDICATE NO OCCUPANCY CHANGE, |
| | (NONE) A R2. UNDER THE ORIGINAL BUILDING PERMIT |
| | 05091265 ALL OF THE FIRST FLOOR UNITS WERE BUILT AS |
| | COMMERCIAL UNITS, PLEASE BE AWARE THERE IS A OCCUPANCY |
| | CHANGE AND THIS REVIEW WILL BE FROM THE |
| | 2010 FBC- EXISTING BUILDING CHAPTER 9 CHANGE OF |
| | OCCUPANCY SECTION 901.3.1 PARTIAL CHANGE OF OCCUPANCY |
| | CLASSIFICATION. WHERE A PORTION OF AN EXISTING BUILDING |
| | IS CHANGED TO A NEW OCCUPANCY CLASSIFICATION, SECTION |
| | 912 SHALL APPLY. PLEASE UPDATE PLANS. |
| | |
| | 2A) SHEETS : |
| | A251A & A401A/ UNIT A |
| | A251B & A401B/ UNIT B |
| | A251D & A401D/ UNIT D |
| | A251E & A401E/ UNIT E |
| | |
| | THE ABOVE STATED PLANS INDICATE THE EXISTING WINDOWS IN |
| | THE BEDROOMS TO BE MODIFIED FOR EGRESS WINDOWS. THIS IS |
| | NOT A CODE REQUIREMENT, THE 2010 FBC-B |
| | 1029.1 EMERGENCY ESCAPE & RESCUE OPENINGS PLEASE REVIEW |
| | EXCEPTION # 1. IN OTHER THAN GROUP R-3 OCCUPANCIES, |
| | BUILDINGS EQUIPPED THROUGHOUT WITH AN APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| | 903.3.1.1 OR 903.3.1.2. |
| | |
| | THE A401 SERIES OF PLANS INDICATES THE SLIDING WINDOW |
| | TO HAVE A CLEAR HEIGHT OF 22 INCHES, 2010 FBC-B |
| | 1029.2.1 MINIMUM DIMENSIONS THE MINIMUM HEIGHT |
| | DIMENSION OF 24" WOULD BE REQUIRED. 24X 30= 720 SQ |
| | INCHES OR THE MINIMUM 5'-0" SQ FT AS REQUIRED FOR THE |
| | GROUND FLOOR. |
| | |
| | 2B) IF THE WINDOWS AND MULLIONS ARE GOING TO BE |
| | REPLACED THEN THE FOLLOWING WIND DESIGN CRITERIA IS |
| | REQUIRED: |
| | |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 2B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 2B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE |
| | 7-10. |
| | |
| | 2B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 2B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 2B)(5) COMPONENTS & CLADDING PRESSURES POSITVE & |
| | NEGATIVE TABLE 1609.2(2) . |
| | |
| | 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) WINDOWS |
| | |
| | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |