| Plan Review Notes For Permit 13070687 |
| Permit Number |
13070687 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-19 06:32:57 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE MAXIMUM DESIGN PRESSURE FOR THE APPROVED | | | ASSEMBLY SPECIFIED ON PAGE 10 OF THE PRODUCT APPROVAL | | | FOR GAF MODIFIED ROOF SYSTEM (NOA NO. 09-0224.01) IS | | | -52.5 PSF. THIS DESIGN PRESSURE IS TOO LOW FOR THE | | | PERIMETER AND CORNER ROOF AREAS FOR THIS STRUCTURE | | | WHICH IS LOCATED IN EXPOSURE CATEGORY "C" WITH A WIND | | | SPEED OF 170 MPH VULT. SUBMIT TWO SETS OF SIGNED AND | | | SEALED RAS 117 FOR ENHANCED FASTENING AS REQUIRED BY | | | LIMITATION NUMBER 7 ON PAGE 31 OF THE PRODUCT APPROVAL. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|