| Plan Review Notes For Permit 13070649 |
| Permit Number |
13070649 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-24 14:41:35 | FIRE ALARM | | | | | | 1781 PALM BEACH LAKES BLVD. | | | FIRE ALARM - PALM BEACH MALL BUILDING J-9 | | | PERMIT #130700649 | | | MASTER #12110064 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | THE ADDRESS IN THE TITLE BLOCK SHOULD REFLECT ONLY | | | 1781, NOT 1741-1801. ALSO, BUILDING SHOULD ONLY BE | | | IDENTIFIED AS J9. | | | | | | NO VISUAL NOTIFICATION PROVIDED IN RESTROOMS, EXCEPT | | | FOR TENANT SPACE W249. DEVICES NEEDED IN ALL RESTROOMS. | | | | | | NO NOTIFICATION APPLIANCES LOCATED IN TENANT SPACES | | | W209, W213, AND W215. | | | | | | NOTIFICATION APPLIANCES IN THE FOLLOWING TENANT SPACES | | | WILL NOT PROVIDE ADEQUATE COVERAGE FOR ENTIRE SPACE: | | | W203, W207, W208, W217, W218, W219, W221, W223, W225, | | | W227, W229, W231, W233, W235, W237, W241, W243, W245, | | | W247, AND W249. | | | | | | NOTIFICATION APPLIANCES IN THE CORRIDORS WILL NOT | | | PROVIDE ADEQUATE COVERAGE FOR TOTAL LENGTH OF CORRIDOR. | | | | | | INDICATE ELEVATION FOR CEILING MOUNTED DEVICES. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|