2013-07-29 13:46:14ADDITIONAL HORNS AND/OR STROBES ARE REQUIRED TO PROVIDE
 NOTIFICATION DEVICES IN EACH TENNANT SPACE. PROVIDE
 STROBES IN BATHROOMS. SHOW INTERCONNECTION OF AIR
 HANDLER SMOKE DETECTOR AND/OR UNIT SHUTDOWN. PLANS SHOW
 2007 NEC?
  
 PLACED IN DENIED UNDER "W" DH