| 2013-08-21 11:59:27 | BUILDING PLAN REVIEW |
| | PERMIT: 13070610 |
| | ADD: 720 S SAPODILLA AV- ROOFTOP |
| | CONT: HAYDEN PROFESSIONAL SERVICES |
| | TEL: (772)781-1512 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: 8/ 21/2012 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. PLANS BEING SUBMITTED FOR CITY REVIEW |
| | REQUIRES CITY PLACE STAMP OF REVIEW AND APPROVAL. |
| | |
| | 2) 2ND REVIEW. SUBMITTED IS A PRE-MANUFACTURED |
| | BUILDING, IT APPEARS NOT TO BE A STATE APPROVED PLAN, |
| | SINCE THERE IS ONLY AN APPROVAL FROM PFS AND ONLY ON A |
| | FEW SHEETS,NOR IS THE SIGNATURE OF THE PLANS EXAMINER |
| | LICENSE NUMBER FOUND ON THE DBPR WEBSITE. THE |
| | ENGINEERING PROVIDED BY JOHN IRVING P. E. DOES INDICATE |
| | THIS STRUCTURE TO BE ELEVATED SINCE THERE IS A HEIGHT |
| | ADJUSTMENT FACTOR OF 1.62. THE ISSUE IS THIS MODULAR |
| | BUILDING IS GOING TO BE LOCATED ON TOP OF AN EXISTING 5 |
| | STORY III-A FULLY SPRINKLERED BUILDING. AS INDICATED |
| | PAGE 1 OF 15 BUILDING TYPE V-B AND BUILDING LIMITATIONS |
| | 1.3.3 OCCUPANCY S-2 OR B OR U FROM THE 2010 FBC-TABLE |
| | 503THIS STRUCTURE CAN NOT BE PLACED ANY HIGHER THAN 2 |
| | STORIES. |
| | THE ORIGINAL BUILDING BEING BUILT AS A MIXED USE |
| | MERCANTILE 1ST FLOOR AND R2 THE SECOND THRU 5TH FLOOR |
| | WHICH ALLOWED FOR 4 STORIES, IT IS FULLY SPRINKLERED |
| | WITH A FULL NFPA 13 SPRINKLER THAT GACE THEM A ONE |
| | STORY INCREASE, THE NEW MODULAR STRUCTURE WOULD ALSO BE |
| | REQUIRED TO BE FULLY SPRINKLERED AND A MINIMUM BUILDING |
| | TYPE OF IIIA. |
| | |
| | 3) 2ND REQUEST.SHEET S2 DETAIL # 5 INDICATES A SPECIAL |
| | PLATE DETAIL OF THE STEEL FRAME BEING ATTACHED TO THE |
| | EXISTING ELEVATOR SHAFT, BUT THERE IS NO INFORMATION AS |
| | TO HOW THE MANUFACTURED BUILDING IS TRANSFERRING THE |
| | LOADS TO THE STRUCTURAL STEEL FRAMEWORK, PART OF THE |
| | MAIN WIND FORCE RESISTING SYSTEM. 2010 1609.4.1. |
| | |
| | 4) 2ND REQUEST. SHEET C4 THE ELEVATIONS INDICATE WHAT |
| | APPEARS TO BE TRIM ON THE CONCEALMENT SCREENS AND |
| | ARCHITECTURAL DECOR TO MATCH THE BUILDING ON THE |
| | MODULAR BUILDING, PLEASE PROVIDE COMPLIANCE WITH: |
| | |
| | 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV |
| | CONSTRUCTION. |
| | ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION, |
| | EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE |
| | CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5, |
| | OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING |
| | WITH THE FOLLOWING LIMITATIONS: |
| | (2.) COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO |
| | 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |