| 2013-07-31 09:15:33 | BUILDING PLAN REVIEW |
| | PERMIT: 13070610 |
| | ADD: 720 S SAPODILLA AV- ROOFTOP |
| | CONT: HAYDEN PROFESSIONAL SERVICES |
| | TEL: (772)781-1512 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 7/31/2012 |
| | ACTION: DENIED |
| | |
| | 1) PLANS BEING SUBMITTED FOR CITY REVIEW REQUIRES CITY |
| | PLACE STAMP OF REVIEW AND APPROVAL. |
| | |
| | 2) THE PLANS INDICATE THE INSTALATION OF A MODULAR |
| | BUILDING BUT NO PLANS WERE SUBMITTED. IF THIS IS A |
| | STATE APPROVED MODULAR BUILDING PLANS STILL NEED TO BE |
| | SUBMITTED WITH THE STATE APPROVAL. NOTE THERE ARE |
| | LIMITATIONS ON STATE APPROVED PLANS REVIEW THE DESIGN |
| | PERAMTERS TO SEE IF IT WAS APPROVED WITH THE ASSOCAITED |
| | PRESSURES BEING PLACED AT THIS ELEVATION. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET S2 DETAIL # 5 INDICATES A SPECIAL PLATE DETAIL |
| | OF THE STEEL FRAME BEING ATTACHED TO THE EXISTING |
| | ELEVATOR SHAFT, BUT THERE IS NO INFORMATION AS TO HOW |
| | THE MANUFACTURED BUILDING IS TRANSFERRING THE LOADS TO |
| | THE STRUCTURAL STEEL FRAMEWORK, PART OF THE MAIN WIND |
| | FORCE RESISTING SYSTEM. 2010 1609.4.1. |
| | |
| | 4) SHEET C4 THE ELEVATIONS INDICATE WHAT APPEARS TO BE |
| | TRIM ON THE CONCEALMENT SCREENS AND ARCHITECTURAL DECOR |
| | TO MATCH THE BUILDING ON THE MODULAR BUILDING, PLEASE |
| | PROVIDE COMPLIANCE WITH: |
| | |
| | 2010 FBC-B 1406.2.2 TYPE I, II, III AND IV |
| | CONSTRUCTION. |
| | ON BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION, |
| | EXTERIOR WALL COVERINGS SHALL BE PERMITTED TO BE |
| | CONSTRUCTED OF WOOD IN ACCORDANCE WITH SECTION 1405.5, |
| | OR OTHER EQUIVALENT COMBUSTIBLE MATERIAL, COMPLYING |
| | WITH THE FOLLOWING LIMITATIONS: |
| | (2.) COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO |
| | 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |