| 2013-07-24 15:29:57 | FBC 2010 EXISTING BUILDING CODE |
| | FBC 2010 ACCESSIBILITY CODE |
| | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. THE TOILET COMPARTMENTS ARE REQUIRED TO CONTAIN A |
| | LAVATORY. THE LAVITORY SHALL NOT BE IN THE REQUIRED |
| | CLEAR SPACE FOR THE WATER CLOSET. |
| | 604.8.1.1 SIZE. |
| | WHEELCHAIR ACCESSIBLE COMPARTMENTS SHALL BE 60 INCHES |
| | (1525 MM) WIDE MINIMUM MEASURED PERPENDICULAR TO THE |
| | SIDE WALL, AND 56 INCHES (1420 MM) DEEP MINIMUM FOR |
| | WALL HUNG WATER CLOSETS AND 59 INCHES (1500 MM) DEEP |
| | MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED |
| | PERPENDICULAR TO THE REAR WALL. |
| | FBC ACCESSIBILITY 2010 604.8.1.6 LAVATORY. |
| | IN NEW CONSTRUCTION, THE WHEELCHAIR ACCESSIBLE TOILET |
| | COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN |
| | IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17 INCHES |
| | DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE LAVATORY |
| | SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR |
| | SPACE AREAS REQUIRED BY SECTION 604 FOR THE WHEELCHAIR |
| | ACCESSIBLE TOILET COMPARTMENT AND SHALL COMPLY WITH |
| | SECTION 606. SUCH LAVATORIES SHALL BE COUNTED AS PART |
| | OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE |
| | ALSO SECTION 213.3.4. |
| | |
| | 2. A HI/LOW DRINKING FOUNTAIN WILL BE REQUIRED. |
| | FBC PLUMBING TABLE 403.1 |
| | FBC ACCESSIBILITY 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |