| Plan Review Notes For Permit 13070567 |
| Permit Number |
13070567 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-07-31 17:33:59 | PLEASE REVISE PLANS AND/OR RESPOND TO THE FOLLOWING | | | COMMENTS. | | | ALL CONSTRUCTION POWER TO BE GFCI PROTECTED 590.6 | | | LIGHTING AND POWER TO BE ON SEPARATE CIRCUITS FOR | | | CONSTRUCTION | | | PROVIDE DETAILS OF FIRE RATED PENETRATIONS, NOT A NOTE | | | ON THE PLAN TO PROPERLY INSTALL | | | SEPARATE PERMITS REQUIRED FOR AUDIO, VISUAL, DATA, POS, | | | ALARM, PHONE, OTHER LOW VOLTAGE | | | |
|