| 2013-12-30 16:45:05 | BUILDING PLAN REVIEW |
| | PERMIT: 13070537 WATER TREATMENT BLDG. |
| | ADD: 6651 N JOG RD |
| | CONT: KBR |
| | TEL: (561 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: MONDAY DEC. 30/2013 |
| | ACTION: DENIED |
| | |
| | 1) LETTER FROM HEAVY STURTURES DESCRIBING WHICH PRODUCT |
| | APPROVALS THEY WERE GOING TO INSTALLDOES NOT MATCH THE |
| | PRODUCT APPROVAL COVER SHEETS SUBMITTED. 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 2) SUBMITTED PRODUCT APPROVAL MIAMI-DADE NOA 10-0901.20 |
| | THE TECHNICAL DRAWINGS WERE NOT LOADED IN LANDSCAPE AND |
| | 1/2 OF THE INFORMATION IS LEFT OFF THE PAGE (6-11) |
| | THE SUB-SYSTEM IS NOT IDENTIFIED BY CIRCLE OR COULD, |
| | PLEASE IDENTIFY WHICH SUB-SYSTEM IS BEING INSTALLED AND |
| | PRESSURES CAN BE VERIFIED. |
| | |
| | 3) MIAMI-DADE NOA 10-0901.18 WAS NEVER SUBMITTED. NOTE |
| | THIS PRODUCT APPROVAL WAS NOT PART OF HEAVY STRUCTURES |
| | APPROVAL LETTER. FLORIDA APPROVAL # FL 12493-R1 BUTLER |
| | PANELWALL, THE SUB-SYSTEM IS NOT IDENTIFIED BY CIRCLE |
| | OR CLOUD. THE EVALUATION REPORT FOR LIMITATION & LOAD |
| | TABLES NOR THE INSTALATION INSTRUCTIONS WERE NOT |
| | UPLOADED. NO REVIEW CAN TAKE PLACE WITHOUT THIS |
| | INFORMATION. |
| | |
| | 4) FLORIDA APPROVAL # FL 12760-R1 BUTLER PANEL WALL/ |
| | LITE PANEL. THE SUB-SYSTEM IS NOT IDENTIFIED BY CIRCLE |
| | OR CLOUD. THE EVALUATION REPORT FOR LIMITATION & LOAD |
| | TABLES NOR THE INSTALATION INSTRUCTIONS WERE NOT |
| | UPLOADED. NO REVIEW CAN TAKE PLACE WITHOUT THIS |
| | INFORMATION. |
| | |
| | 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. ROLL UP DOORS, SWING DOORS, |
| | ROOF HATCHES |
| | (C) WALLS: SIDING , WALL LOUVERS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES CURBS FOR ROOF TOP |
| | FANS |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |