2013-08-10 19:30:086610 NORTH JOG ROAD - ASH MANAGEMENT BUILDING
 PERMIT #13070532
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLEASE PROVIDE A WRITTEN NARRATIVE SUMMARIZING THE
 ENGINEERING CONTROLS (AUTOMATIC SPRINKLER SYSTEM,
 MAGNETIC SEPARATOR, DUST COLLECTORS, PRESSURE RELIEF
 PANELS, BONDING/GROUNDING, SPARK ARRESTORS, ABORT
 GATES, ETC.) THAT ARE BEING IMPLEMENTED TO MITIGATE
 PROBABILITY AND SEVERITY OF A COMBUSTIBLE DUST FIRE
 AND/OR EXPLOSION.
  
 DESIGN SHALL CONFORM TO THE REQUIREMENTS OF NFPA 1 -
 CHAPTER 40: DUST EXPLOSION AND FIRE PREVENTION. A FEW
 OF THE REQUIREMENTS HAVE BEEN INDICATED BELOW.
  
 PER NFPA 1 SECTION 40.1, EQUIPMENT, PROCESSES, AND
 OPERATIONS THAT INVOLVE THE MANUFACTURE, PROCESSING,
 BLENDING, REPACKAGING, OR HANDLING OF COMBUSTIBLE
 PARTICULATE SOLIDS OR COMBUSTIBLE DUSTS REGARDLESS OF
 CONCENTRATION OR PARTICLE SIZE SHALL BE INSTALLED AND
 MAINTAINED IN ACCORDANCE WITH THIS CHAPTER AND THE
 FOLLOWING STANDARDS AS APPLICABLE: NFPA 69 - STANDARD
 ON EXPLOSION PREVENTION SYSTEMS & NFPA 654 - STANDARD
 FOR THE PREVENTION OF FIRE AND DUST EXPLOSIONS FROM THE
 MANUFACTURING, PROCESSING, AND HANDLING OF COMBUSTIBLE
 PARTICULATE SOLIDS.
  
 PER NFPA 1 SECTION 40.3.2.1.2, REGULAR CLEANING
 FREQUENCIES SHALL BE ESTABLISHED FOR WALLS, FLOORS, AND
 HORIZONTAL SURFACES, SUCH AS EQUIPMENT, DUCTS, PIPES,
 HOODS, LEDGES, BEAMS, AND ABOVE SUSPENDED CEILINGS AND
 OTHER CONCEALED SURFACES, TO MINIMIZE DUST
 ACCUMULATIONS WITHIN OPERATING AREAS OF THE FACILITY.
  
 PER NFPA 1 SECTION 40.3.2.2, SURFACES SHALL BE CLEANED
 IN A MANNER THAT MINIMIZES THE GENERATION OF DUST
 CLOUDS. VIGOROUS SWEEPING OR BLOWING DOWN WITH STEAM OR
 COMPRESSED AIR PRODUCES DUST CLOUDS AND SHALL BE
 PERMITTED ONLY WHERE THE FOLLOWING REQUIREMENTS ARE
 MET:
 (1) AREA AND EQUIPMENT SHALL BE VACUUMED PRIOR TO
 BLOWDOWN.
 (2) ELECTRICAL EQUIPMENT NOT SUITABLE FOR CLASS II
 LOCATIONS AND OTHER SOURCES OF IGNITION SHALL BE SHUT
 DOWN OR REMOVED FROM THE AREA.
 (3) ONLY LOW-PRESSURE STEAM OR COMPRESSED AIR, NOT
 EXCEEDING A GAUGE PRESSURE OF 15 PSI (103 KPA), SHALL
 BE USED.
 (4) NO HOT SURFACES OR FLAMES CAPABLE OF IGNITING A
 DUST CLOUD OR LAYER SHALL EXIST IN THE AREA.
  
 PER NFPA 1 SECTION 40.3.2.3, VACUUM CLEANERS SHALL BE
 LISTED FOR USE IN CLASS II HAZARDOUS LOCATIONS OR SHALL
 BE A FIXED-PIPE SUCTION SYSTEM WITH REMOTELY LOCATED
 EXHAUSTER AND DUST COLLECTOR.
  
 PER NFPA 1 - 40.4.8 INDUSTRIAL TRUCKS. IN AREAS
 CONTAINING A COMBUSTIBLE DUST HAZARD, ONLY INDUSTRIAL
 TRUCKS LISTED OR APPROVED FOR THE ELECTRICAL
 CLASSIFICATION OF THE AREA, AS DETERMINED BY SECTION
 6.6 OF NFPA 654, SHALL BE USED IN ACCORDANCE WITH NFPA
 505, FIRE SAFETY STANDARD FOR POWERED INDUSTRIAL TRUCKS
 INCLUDING TYPE DESIGNATIONS, AREAS OF USE, CONVERSIONS,
 MAINTENANCE, AND OPERATIONS.
  