| 2013-08-25 09:54:19 | BUILDING PLAN REVIEW |
| | PERMIT: 13070531 |
| | ADD: 6751 N JOG RD |
| | CONT: HEDRICK BROTHERS |
| | TEL: (561)###-#### |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SUNDAY/ AUGUST 25/ 2013 |
| | ACTION: BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | TYPE BUILDING: II-B |
| | SPRINKLERED |
| | |
| | 1) (20) SHEET 710-A2-100 FINISH SCHEDULE |
| | SEE: |
| | CORRIDOR C-200- CARPET TILE |
| | CONFERENCE RM C-201-CARPET TILE |
| | EAST STAIR- RUBBER TILE |
| | PLEASE SHOW COMPLIANCE WITH: |
| | 2010 FBC-B TABLW 803.9 FLOOR FINISHES FOR OCCUPANCY |
| | TYPE A3/ SPRINKLERED BUILDING |
| | EXIT ENCLOSURES- B |
| | CORRIDORS- B |
| | ENCLOSED SPACES- C |
| | |
| | ALSO SECTION 804.4.1 MINIMUM CRITICAL RADIANT FLUX. |
| | INTERIOR FLOOR FINISH AND FLOOR COVERING MATERIALS IN |
| | EXIT ENCLOSURES, EXIT PASSAGEWAYS AND CORRIDORS SHALL |
| | NOT BE LESS THAN CLASS I IN GROUPS I-1, I-2 AND I-3 AND |
| | NOT LESS THAN CLASS II IN GROUPS A, B, E, H, M, R-1, |
| | R-2 AND S. IN ALL AREAS, FLOOR COVERING MATERIALS SHALL |
| | COMPLY WITH THE DOCFF-1 ?PILL TEST? (CPSC 16 CFR, PART |
| | 1630). |
| | |
| | 2) (23)710-A3-102 ELEVATIONS INDICATE THE USE OF 2 INCH |
| | MOUNTED WIRE MESH IN-FILL MOUNTED IN STEEL FRAME |
| | CHANNEL FRAME, THE ARCHITECTURAL NOR STRUCTURAL SHEETS |
| | SHOW COMPLIANCE WITH 2010 FBC-B 1607.7.1.2 COMPONENTS. |
| | INTERMEDIATE RAILS (ALL THOSE EXCEPT THE HANDRAIL), |
| | BALUSTERS AND PANEL FILLERS SHALL BE DESIGNED TO |
| | WITHSTAND A HORIZONTALLY APPLIED NORMAL LOAD OF 50 |
| | POUNDS (0.22 KN) ON AN AREA EQUAL TO 1 SQUARE FOOT |
| | (0.0929 M2), INCLUDING OPENINGS AND SPACE BETWEEN |
| | RAILS. REACTIONS DUE TO THIS LOADING ARE NOT REQUIRED |
| | TO BE SUPERIMPOSED WITH THOSE OF SECTION 1607.7.1 OR |
| | 1607.7.1.1. |
| | |
| | 3) (28) 710-A3-107 SECTION # 1 EAST STAIR INDICATES A |
| | SUSPENDED ACCENT CANOPY IN THE STAIRWELL, PLEASE SHOW |
| | COMPLIANCE WITH; |
| | 2010 FBC-B TABLE 803.9 CEILINGS |
| | EXIT ENCLOSURE, A3/ SPRINKLERED TYPE "A" FINISHES. |
| | |
| | ALSO COMPLIANCE WITH SECTION: 2010 FBC-B 806.1 GENERAL |
| | REQUIREMENTS. |
| | IN OCCUPANCIES IN GROUPS A, E, I AND R-1 AND |
| | DORMITORIES IN GROUP R-2, CURTAINS, DRAPERIES, HANGINGS |
| | AND OTHER DECORATIVE MATERIALS SUSPENDED FROM WALLS OR |
| | CEILINGS SHALL MEET THE FLAME PROPAGATION PERFORMANCE |
| | CRITERIA OF NFPA 701 IN ACCORDANCE WITH SECTION 806.2 |
| | OR BE NONCOMBUSTIBLE. |
| | |
| | 4) (74) 710-S3-202 SECTION # 1 ALUMINUM GAURDRAIL |
| | SYSTEM, AND MOUNTING PLATE, PLANS DO NOT SHOW |
| | COMPLIANCE WITH : 2010 FBC-B 1607.7.1.1 CONCENTRATED |
| | LOAD. |
| | HANDRAILS AND GUARDS SHALL BE ABLE TO RESIST A SINGLE |
| | CONCENTRATED LOAD OF 200 POUNDS (0.89 KN), APPLIED IN |
| | ANY DIRECTION AT ANY POINT ALONG THE TOP, AND TO |
| | TRANSFER THIS LOAD THROUGH THE SUPPORTS TO THE |
| | STRUCTURE. THIS LOAD NEED NOT BE ASSUMED TO ACT |
| | CONCURRENTLY WITH THE LOADS SPECIFIED IN SECTION |
| | 1607.7.1. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | PLEASE PROVIDE COMPLIANCE WITH |
| | |
| | EXCEPTION: WHERE A BUILDING IS EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 OR 903.3.1.2, CLASS II MATERIALS ARE |
| | PERMITTED IN ANY AREA WHERE CLASS I MATERIALS ARE |
| | REQUIRED, AND MATERIALS COMPLYING WITH THE DOC FF-1 |
| | ?PILL TEST? (CPSC 16 CFR, PART 1630) ARE PERMITTED IN |
| | ANY AREA WHERE CLASS II MATERIALS ARE REQUIRED. |
| | |
| | |
| | |